Emerson 00825-0100-4530 Rev EC manual FOUNDATION fieldbus parameters

Page 17
FOUNDATION fieldbus parameters:

March 2013

Quick Installation Guide

are normally configured at the factory, but can be changed if, for example, the probe is cut in the field, or if disturbing objects in the near zone need to be blocked out (Hold Off Distance/Upper Null Zone (UNZ)).

Handheld HART Communicator: Fast Key Sequence [2, 1, 2].

FOUNDATION fieldbus parameters:

TRANSDUCER_1100 > PROBE_TYPE

TRANSDUCER_1100 > PROBE_LENGTH

TRANSDUCER_1100 > GEOM_HOLD_OFF_DIST

Click Next and the following window appears (Geometry).

7.Enter Tank Height, the distance from the Upper Reference Point to the Lower Reference Point (which is the tank bottom in the screenshot above), making sure it is as accurate as possible. See Configuration in the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530) for details.

Set Mounting Type. Set Diameter if Mounting Type is Nozzle or Pipe/Chamber. Set Nozzle Height if Mounting Type is Nozzle.

Handheld HART Communicator: Fast Key Sequence [2, 1, 3]

FOUNDATION fieldbus parameters:

TRANSDUCER_1100 > GEOM_TANK_HEIGHT

TRANSDUCER_1100 > MOUNTING_TYPE

TRANSDUCER_1100 > PIPE_DIAMETER

TRANSDUCER_1100 > NOZZLE_HEIGHT

17

Image 17
Contents Quick Installation Guide 00825-0100-4530,Rev EC MarchSuperior Performance Guided Wave Radar Level and Interface TransmitterProbes with non-conductingsurfaces About this guideQuick Installation Guide March ContentsStep 1: Confirm system readiness Switch HART revision modeConfirm HART revision capability Confirm correct Device DriverTank connection with flange Step 2 Mount the transmitter head/probeThreaded tank connection Tri-Clamptank connectionBracket mounting, on pipe Step 2 continuedBracket mounting, on wall Step 2 continued Remote housingGrounding Step 3 Connect the wiringTerminal block To connect the transmitterIntrinsically safe power supply Non-intrinsicallysafe power supplyHART communication Step 3 continuedQuick Installation Guide Transient protection terminal blockPower PowerQuick Installation Guide Load limitationsNon-HazardousInstallations InstallationsIntrinsically safe power supply Step 3 continued FOUNDATION fieldbusNon-intrinsicallysafe power supply Power Consumption 0.5 W with HART address = RS-485with Modbus communicationQuick Installation Guide Step 3 continuedInstalling the Rosemount Radar Master software Step 4 Configure1Only for HART communication Run WizardFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters 3.Click Modbus Setup Setup - Modbus communication parametersConfiguration Safety Instrumented Systems 4-20mA onlyInstallation Table 3. Alarm levels and operation values Alarm and saturation levelsDamping Write protectionProof test Operation and maintenanceSite acceptance Inspection SpecificationsReferences Visual inspectionProduct certifications Safety Instrumented Systems SISEU conformity North-AmericancertificationsQuick Installation Guide Canadian Standards Association CSA approvalsDual seal maintenance I5, IE1 Intrinsically safe and FISCO modelATEX approvals European certificationsMarch Special conditions for safe useINMETRO approvals Brazilian certificationsQuick Installation Guide Special conditions for safe useMarch Chinese certificationsI21 Intrinsically safe IB1 FISCO modelQuick Installation Guide Japanese certificationsIC1 FOUNDATION fieldbus FISCO model N3 Type nIECEx approvals IECEx certificationsMarch Special conditions for safe useOverfill protection Other certificationsQuick Installation Guide Suitability for intended useFigure 1. EC Declaration of Conformity - page EC Declaration of ConformityQuick Installation Guide MarchMarch Figure 2. EC Declaration of Conformity - pageQuick Installation Guide March Figure 3. EC Declaration of Conformity - pageQuick Installation Guide 00825-0100-4530 Quick Installation Guide00825-0100-4530,Rev EC March Emerson Process Management Rosemount Measurement