Emerson 00825-0100-4530 Rev EC manual Inspection, References, Visual inspection, Special tools

Page 24

Quick Installation Guide

March 2013

 

 

6.Enable write protection.

7.Restore the loop to full operation.

8.Remove the bypass from the safety logic solver or otherwise restore normal operation.

9.Document the test result for future reference.

Inspection

Visual inspection

It is recommended to inspect the probe for possible build up or clogging.

Special tools

Not required.

Product repair

All failures detected by the transmitter diagnostics or by the proof test must be reported. Feedback can be submitted electronically at www.emersonprocess.com/rosemount/safety (Contact Us).

The Rosemount 5300 Series is repairable by complete transmitter head replacement. Contact your local Emerson Process Management representative to perform the replacement. Additional information is available in the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530).

References

Specifications

The Rosemount 5300 must be operated in accordance with the functional and performance specifications provided in the Rosemount 5300 Series Reference Manual (Document No. 00809-0100-4530), Appendix A: Reference Data.

Failure rate data

The FMEDA report includes failure rates and common cause Beta factor estimates. The full report is accessible at www.emersonprocess.com/rosemount/safety/PriorUse.htm.

Useful lifetime

The established failure rates of electrical components apply within the useful lifetime, which should be based on experience. According to IEC 61508-2, 7.4.7.4, note 3, the useful lifetime often lies within a range of 8 to 12 years for transmitters.

24

Image 24
Contents 00825-0100-4530,Rev EC March Quick Installation GuideSuperior Performance Guided Wave Radar Level and Interface TransmitterAbout this guide Quick Installation GuideProbes with non-conductingsurfaces Contents MarchSwitch HART revision mode Step 1: Confirm system readinessConfirm HART revision capability Confirm correct Device DriverStep 2 Mount the transmitter head/probe Tank connection with flangeThreaded tank connection Tri-Clamptank connectionStep 2 continued Bracket mounting, on wallBracket mounting, on pipe Remote housing Step 2 continuedStep 3 Connect the wiring GroundingTo connect the transmitter Terminal blockNon-intrinsicallysafe power supply Intrinsically safe power supplyHART communication Step 3 continuedTransient protection terminal block Quick Installation GuidePower PowerLoad limitations Quick Installation GuideNon-HazardousInstallations InstallationsStep 3 continued FOUNDATION fieldbus Non-intrinsicallysafe power supplyIntrinsically safe power supply RS-485with Modbus communication Power Consumption 0.5 W with HART address =Quick Installation Guide Step 3 continuedStep 4 Configure Installing the Rosemount Radar Master softwareRun Wizard 1Only for HART communicationFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters Setup - Modbus communication parameters 3.Click Modbus SetupSafety Instrumented Systems 4-20mA only InstallationConfiguration Alarm and saturation levels Table 3. Alarm levels and operation valuesDamping Write protectionOperation and maintenance Site acceptanceProof test Specifications InspectionReferences Visual inspectionSafety Instrumented Systems SIS Product certificationsEU conformity North-AmericancertificationsCanadian Standards Association CSA approvals Quick Installation GuideDual seal maintenance I5, IE1 Intrinsically safe and FISCO modelEuropean certifications ATEX approvalsMarch Special conditions for safe useBrazilian certifications INMETRO approvalsQuick Installation Guide Special conditions for safe useChinese certifications MarchI21 Intrinsically safe IB1 FISCO modelJapanese certifications Quick Installation GuideIC1 FOUNDATION fieldbus FISCO model N3 Type nIECEx certifications IECEx approvalsMarch Special conditions for safe useOther certifications Overfill protectionQuick Installation Guide Suitability for intended useEC Declaration of Conformity Figure 1. EC Declaration of Conformity - pageQuick Installation Guide MarchFigure 2. EC Declaration of Conformity - page Quick Installation GuideMarch Figure 3. EC Declaration of Conformity - page Quick Installation GuideMarch Quick Installation Guide 00825-0100-453000825-0100-4530,Rev EC March Emerson Process Management Rosemount Measurement