March 2013 | Quick Installation Guide |
|
|
Product certifications
EU conformity
The EC declaration of conformity can be found on page 33. The most recent revision of the EC declaration of conformity can be found at www.rosemount.com.
Safety Instrumented Systems (SIS)
The Rosemount 5300 Series has been evaluated by a third party, Exida, against hardware requirements according to IEC 61508. With a FMEDA (Failure Modes, Effects and Diagnostics Analysis) report with a Safe Failure Fraction (SFF) above 90%, 5300 is suitable in SIS according to the Prior Use methodology. For more information, go to: http://emersonprocess.com/rosemount/safety/. To order the certificate of FMEDA data, use option code QS.
Hazardous Locations certifications
North-American certifications
Factory Mutual (FM) approvals
Project ID: 3020497
Specific conditions of use:WARNING: Potential Electrostatic Charging Hazard - The enclosure is constructed from plastic. To prevent the risk of electrostatic sparking, the plastic surface should only be cleaned with a damp cloth.
WARNING: The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.
E51Groups B, C, and D;
With Intrinsically Safe connections to
Class I, II, III, Div. 1, Groups B, C, D, E, F, and G.
Temp. Code T4
Ambient temperature limits:
Seal not required.
Approval valid for HART, FOUNDATION fieldbus, and Modbus options.
1)Ordering information code for Product Certifications, see the Rosemount 5300 Series Product Data Sheet (Document No.
(Document No.
2)+60 °C with FOUNDATION fieldbus or FISCO option.
25