Emerson 00825-0100-4530 Rev EC HART communication, continued, Non-intrinsicallysafe power supply

Page 10
Step 3 continued...

Quick Installation Guide

March 2013

 

 

Step 3 continued...

HART communication

The Rosemount 5300 Series transmitter operates with a power supply ranging from 16 - 42.4 Vdc (16 - 30 Vdc in IS applications, 20-42.4 Vdc in Explosion-proof / Flameproof applications and in Non-Sparking / Energy Limited applications).

All configuration tools for HART communication, such as the Field Communicator and Rosemount Radar Master, require a minimum load resistance (RL) of 250 Ω within the loop in order to function properly, see diagrams below.

Non-intrinsically safe power supply

 

 

 

Field

Rosemount 5300 Series

 

 

PC

Communicator

Transmitter

 

 

 

 

 

 

HART

 

 

 

 

Modem

 

 

Power

Load Resistance

 

 

Supply

 

 

250

Ω

 

 

 

 

 

NOTE:

Rosemount 5300 Series Transmitters with Flameproof/Explosion-proof output have a built-in barrier; no external barrier needed.

Intrinsically safe power supply

 

 

 

Field

Rosemount 5300 Series

 

PC

Communicator

Transmitter

 

HART

 

 

 

 

Modem

 

Power

 

 

 

 

Supply

RL=250

Ω

 

 

 

 

 

ApprovedIS

Barrier

For IS Parameters, see the Product certifications chapter.

10

Image 10
Contents Superior Performance Guided Wave Radar 00825-0100-4530,Rev EC MarchQuick Installation Guide Level and Interface TransmitterQuick Installation Guide About this guideProbes with non-conductingsurfaces Contents MarchConfirm HART revision capability Switch HART revision modeStep 1: Confirm system readiness Confirm correct Device DriverThreaded tank connection Step 2 Mount the transmitter head/probeTank connection with flange Tri-Clamptank connectionBracket mounting, on wall Step 2 continuedBracket mounting, on pipe Remote housing Step 2 continuedStep 3 Connect the wiring GroundingTo connect the transmitter Terminal blockHART communication Non-intrinsicallysafe power supplyIntrinsically safe power supply Step 3 continuedPower Transient protection terminal blockQuick Installation Guide PowerNon-HazardousInstallations Load limitationsQuick Installation Guide InstallationsNon-intrinsicallysafe power supply Step 3 continued FOUNDATION fieldbusIntrinsically safe power supply Quick Installation Guide RS-485with Modbus communicationPower Consumption 0.5 W with HART address = Step 3 continuedStep 4 Configure Installing the Rosemount Radar Master softwareRun Wizard 1Only for HART communicationFOUNDATION fieldbus parameters FOUNDATION fieldbus parameters FOUNDATION fieldbus parameters Setup - Modbus communication parameters 3.Click Modbus SetupInstallation Safety Instrumented Systems 4-20mA onlyConfiguration Damping Alarm and saturation levelsTable 3. Alarm levels and operation values Write protectionSite acceptance Operation and maintenanceProof test References SpecificationsInspection Visual inspectionEU conformity Safety Instrumented Systems SISProduct certifications North-AmericancertificationsDual seal maintenance Canadian Standards Association CSA approvalsQuick Installation Guide I5, IE1 Intrinsically safe and FISCO modelMarch European certificationsATEX approvals Special conditions for safe useQuick Installation Guide Brazilian certificationsINMETRO approvals Special conditions for safe useI21 Intrinsically safe Chinese certificationsMarch IB1 FISCO modelIC1 FOUNDATION fieldbus FISCO model Japanese certificationsQuick Installation Guide N3 Type nMarch IECEx certificationsIECEx approvals Special conditions for safe useQuick Installation Guide Other certificationsOverfill protection Suitability for intended useQuick Installation Guide EC Declaration of ConformityFigure 1. EC Declaration of Conformity - page MarchQuick Installation Guide Figure 2. EC Declaration of Conformity - pageMarch Quick Installation Guide Figure 3. EC Declaration of Conformity - pageMarch 00825-0100-4530,Rev EC March Quick Installation Guide00825-0100-4530 Emerson Process Management Rosemount Measurement