March 2013 | Quick Installation Guide |
IECEx certifications
IECEx approvals
Special conditions for safe use (X)
The intrinsically safe circuits do not withstand the 500 V AC test as specified in IEC
Impact and friction hazards need to be considered according to EN
The Ex ia version of model 5300 FISCO field device may be supplied by an [Ex ib] FISCO power supply when the power supply is certified with three separate safety current limiting devices and voltage limitation which meets the requirements for type Ex ia.
E71 Flameproof:
IECEx NEM 06.0001X
Ex ia/db ia IIC T4 Ga/Gb
Ex ta IIIC T 79 °C3
Um = 250 V.
Approval valid for HART, FOUNDATION fieldbus, and Modbus options.
I7, IG1 Intrinsically safe and FISCO model:
IECEx NEM 06.0001X
Ex ia IIC T4
Ex ia/ib IIC T4 Ga/Gb
FOUNDATION fieldbus model: Ui = 30 Vdc, Ii = 300 mA, Pi = 1.5 W, Ci = 4.95 nF, Li = 0 H.
FISCO model: Ui = 17.5 Vdc, Ii = 380 mA, Pi = 5.32 W, Ci = 4.95 nF, Li < 1 μH.
Installation Drawing: 9240
Approval valid for HART, FOUNDATION fieldbus, and FISCO options.
N71 Type n:
Ex nAnL IIC T4
FOUNDATION fieldbus model: Un = 32 V
Approval valid for HART and FOUNDATION fieldbus options.
1)Ordering information code for Product Certifications, see the Rosemount 5300 Series Product Data Sheet (Document No.
(Document No.
2)+60 °C with FOUNDATION fieldbus or FISCO option.
3)+69 °C with FOUNDATION fieldbus or FISCO option.
31