Hoshizaki KM-901MWH, KM-901MAH Bin Control Check, Control Correct LED Board Lighting Sequence

Page 54

3)The "OUTPUT TEST" button provides a relay sequence test. Make sure the control switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct lighting sequence, see the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. Components (e.g., compressor) cycle during the test.

Control

Correct LED

Board

Lighting Sequence

 

 

"E"

2, 3, 4, 1

 

 

"G"

1, 4, 3, 2

Following the test, the icemaker resumes operation. If the LEDs do not light as described above, the control board is bad and should be replaced. See "V.P. Removal and Replacement of Control Board."

4)To verify voltage output from the control board to the components, slide the control board K1 tenpin connector out far enough to allow multimeter lead contact. With the unit in the cycle to be tested, check output voltage from the corresponding pin on the control board K1 tenpin connector to ground. If output voltage is not found and the appropriate LED is on, the control board is bad and should be replaced. See "V.P. Removal and Replacement of Control Board."

C.Bin Control Check

1.Thermostatic Bin Control Check: Auxiliary Code T-0,U-0To check the thermostatic bin control, follow the steps below.

CAUTION

When the ambient temperature is below 45°F (7°C), the thermostatic bin control switch opens and shuts down the icemaker even if the ice storage bin is empty. When the thermostat is set in the prohibited range, the icemaker operates continuously even if the ice storage bin is filled with ice. Setting in the prohibited range may result in severe damage to the icemaker.

The thermostatic bin control is factory set, and generally no adjustment is required. However, adjustment may be needed in some conditions, particularly at higher altitude locations.

1)Turn off the power supply.

2)Remove the front panel, then remove the control box cover.

3)Disconnect the thermostatic bin control wires from the thermostatic bin control switch.

4)Clear any ice away from the thermostatic bulb, then hold your hand around the thermostatic bulb to warm it up.

5)Check for continuity across the thermostatic bin control switch. If closed, continue to step 6. If open, adjust or replace the thermostatic bin control.

6)With the multimeter test leads still in place, hold ice on the thermostatic bulb to lower the temperature. Within 10 seconds, the thermostatic bin control switch should open (no continuity). If it remains closed, adjust or replace the thermostatic bin control.

54

Image 54
Contents KM-901MAH KM-901MWH Hoshizaki AMERICA, INC Contents Page Page Indicates important information about the use and care Important Safety InformationSerious injury UnitSpecifications Icemaker 1a. KM-901MAH air-cooled Auxiliary Code T-0, U-01b. KM-901MAH air-cooled Auxiliary Code U-1 and Later 2a. KM-901MWH water-cooled Auxiliary Code T-0, U-0 Water Cooled Condenser2b. KM-901MWH water-cooled Auxiliary Code U-1 and Later 3a. KM-901MRH remote air-cooled Auxiliary Code T-0, U-0 3b. KM-901MRH remote air-cooled Auxiliary Code U-1 and Later 4a. KM-901MRH3 remote air-cooled Auxiliary Code T-0, U-0 4b. KM-901MRH remote air-cooled Auxiliary Code U-1 and Later Condenser Unit Specifications Model URC-9FII. General Information Construction KM-901MAH air-cooledKM-901MWH water-cooled KM-901MRH/3 remote air-cooled Sequence of Operation Sequence Cycles and ShutdownControl Board Auxiliary Code T-0, U-0 Shutdown Control Board Auxiliary Code U-1 and LaterOFF Cycle at Shutdown Mechanical Bin Control Activation Cycle Control Board Sequence Flow ChartSequence Flow Chart Bin FullMinute Harvest Cycle Freeze Cycle Pump-Out Cycle Control Board Auxiliary Code U-1Later Fill CycleControl Board Control Board Layout Control BoardPart Number 2A3792-01 Low Water Safety Harvest Backup Timer and Freeze TimerHigh Temperature Safety Maximum Water Supply Period 6 minutesSequence Step LED Lights and Audible Alarm SafetiesNo. of Beeps Type of Alarm Every 3 sec Energized Time LEDs are On Components Min Max AvgControl Board Auxiliary Code U-1 and Later Harvest Timer S4 dip switch 1 Controls and AdjustmentsDefault Dip Switch Settings S4 Dip Switch S4 Dip Switch NoPump-Out Timer S4 dip switch 3 Pump-Out Frequency Control S4 dip switch 5S4 Dip Switch Setting Time seconds Inlet Control Board S4 Dip Switch Setting Bin Control Bin Control Selector/Harvest Pump Timer S4 dip switchFactory Use S4 dip switch Control Board S4 Dip Switch Setting Pump Motor Time secondsRefill Counter S5 dip switch 2 through 5 G Control Board Freeze Timer S4 dip switch 9Float Switch Control S5 dip switch 1 G Control Board S4 Dip Switch Setting Time MinutesBin Control Float SwitchControl Switch ThermistorWater Pump Switch Discharge Line Wiring Diagrams ModelCooled-AirWater-Cooled Model PressureHigh* SwitchKM-901MAH air-cooled and KM-901MWH water-cooled PressureSwitch KM-901MRH remote air-cooledHigh KM-901MRH3 remote air-cooled Switch Cooled-WaterModel Cooled-AirModel High* PressureHigh Pressure Switch SwitchPressure Performance Data 1480 912835 1570KM-901MRH remote air-cooled KM-901MRH3 remote air-cooled IV. Service Diagnosis Diagnostic ProcedurePage OFF Control Board Check Shutdown Thermostatic Bin Control Auxiliary Code T-0, U-0Bin Control Check Control Correct LED Board Lighting SequenceMechanical Bin Control Check Mechanical Bin Control Cleaning Float Switch Check and Cleaning Float Switch CheckFloat Switch Cleaning Thermistor Check Diagnostic Charts Problem Possible Cause RemedyNo Ice Production Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Problem Possible Cause Remedy Low Ice Production Abnormal Ice Other Removal and Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Brazing Evacuation and Recharge R-404ARemoval and Replacement of Compressor Removal and Replacement of Expansion Valve Page Removal and Replacement of Evaporator Removal and Replacement of Air-Cooled Condenser Removal and Replacement of Water-Cooled Condenser Removal and Replacement of Remote Air-Cooled Condenser Page Adjustment of Water Regulating Valve water-cooled model Removal and Replacement of Thermistor Removal and Replacement of Inlet Water Valve Removal and Replacement of Pump Motor Removal and Replacement of Control Board VI. Cleaning and Maintenance Cleaning and Sanitizing InstructionsCleaning Procedure Sanitizing Procedure Following Cleaning Procedure Maintenance Preparing the Icemaker for Long StorageDrain the water tank