Hoshizaki KM-901MAH, KM-901MWH Control Board Auxiliary Code U-1, Later, Fill Cycle, Icemaker Off

Page 25

"G" Control Board Sequence Flow Chart KM-901MAH, KM-901MWH, KM-901MRH/3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cycle Steps

 

 

 

 

1. 1-Minute

2. Harvest Cycle

3. Freeze Cycle

 

 

4. Pump-Out Cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

• WV time: 6 min. or the length of harvest minus 0 or

 

 

 

 

 

 

 

 

 

 

Fill Cycle

 

 

50 sec. (S4 dip switch 7), whichever is shorter. DO

 

• Minimum freeze time: 5 min.

• Factory set for every

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT ADJUST S4 dip switch 7 on this model.

 

• Maximum freeze time: freeze timer setting

10th cycle (S4 dip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(S4 dip switch 9 & 10)

 

 

switch 5 & 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Maximum harvest time: 20 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Pump motor stops

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermistor in

 

 

 

 

1 to 3-min. timer in control

 

 

 

 

 

5-min. timer

 

 

 

 

 

F/S in control

 

for 2 sec., then

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control

 

 

 

 

(S4 dip switch 1 & 2)

 

 

in control

 

 

 

 

 

reverses for 10/20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Harvest Pump

 

 

 

 

 

 

 

 

 

 

 

 

sec. (S4 dip switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timer

 

 

 

 

 

 

 

 

 

 

 

 

3 & 4)

 

 

Initial startup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 or 50 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

begins here

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

after 5-sec.

 

 

 

 

F/S check

 

 

F/S closed

 

 

 

 

 

 

PM energized F/S check

 

F/S closed

 

 

 

 

 

 

 

F/S open or freeze

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WV de-energized

 

 

 

 

 

 

 

 

 

 

Comp continues

 

WV energized

 

WV continues

 

 

 

 

 

Comp continues

timer expires

 

 

 

 

 

 

 

Thermistor temperature

 

FMR continues

 

 

 

 

 

 

 

 

 

 

 

 

 

Comp energized

reaches 48°F (9°C) (3.9 kΩ

 

FMR continues

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGV energized

 

 

 

 

 

 

 

 

 

 

F/S open

 

FMR energized

or less). Harvest timer starts.

 

PM energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM de-energizes for 2 sec.,

 

 

 

 

 

 

 

 

 

 

 

HGV energized

 

FMS energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then reverses for 10/20 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLV energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FM de-energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F/S open

 

HGV de-energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLV de-energized

25

 

 

 

 

 

 

If F/S is open, compressor stops and cycle returns to 1-Minute Fill Cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b) "G" Control Board: Auxiliary Code U-1 and

Shutdown and Restart

MBC Operation

1. Bin Full

Shutdown Delay:

Fill Cycle–15 sec. after activation.

Harvest Cycle–At the end of the harvest cycle, or up to 15 sec. into the freeze cycle if activated at the end of the harvest cycle.

Freeze Cycle–15 sec. after activation if activated at least 15 sec. before the

5-min. short cycle protection timer expires. Otherwise, at the end of the next harvest cycle.

2. Icemaker Off

All components de-energized.

3. Ice Level Lowered

Ice level lowered. No ice pressing against MBC actuator paddle. Icemaker starts at

"1. 1-Minute Fill Cycle."

To 1 above

Later

MBC open

Green "BC CLOSED" LED off

Yellow "BC OPEN" LED on

Legend:

Comp–compressor

FM–fan motor

FMR–fan motor-remote

F/S–float switch

HGV–hot gas valve

LLV–liquid line valve

MBC–mechanical bin control

PM–pump motor

WV–inlet water valve

Yellow "BC OPEN" LED continues.

MBC closed

All components deenergized

Green "BC CLOSED" LED on

 

Yellow "BC OPEN" LED off

Components Energized when the Control Switch is in the "WASH" Position

The "WASH" position on the control switch is used when cleaning and sanitizing the unit. When in the "WASH" position, power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer flow over the outside of the evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer flow over both the outside and the inside of the evaporator plate assembly.

Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not restart when the control switch is placed in the "ICE" position.

Image 25
Contents KM-901MAH KM-901MWH Hoshizaki AMERICA, INC Contents Page Page Serious injury Important Safety InformationIndicates important information about the use and care Unit1a. KM-901MAH air-cooled Auxiliary Code T-0, U-0 Specifications Icemaker1b. KM-901MAH air-cooled Auxiliary Code U-1 and Later Water Cooled Condenser 2a. KM-901MWH water-cooled Auxiliary Code T-0, U-02b. KM-901MWH water-cooled Auxiliary Code U-1 and Later 3a. KM-901MRH remote air-cooled Auxiliary Code T-0, U-0 3b. KM-901MRH remote air-cooled Auxiliary Code U-1 and Later 4a. KM-901MRH3 remote air-cooled Auxiliary Code T-0, U-0 4b. KM-901MRH remote air-cooled Auxiliary Code U-1 and Later Condenser Unit Model URC-9F SpecificationsKM-901MAH air-cooled II. General Information ConstructionKM-901MWH water-cooled KM-901MRH/3 remote air-cooled Sequence Cycles and Shutdown Sequence of OperationControl Board Auxiliary Code T-0, U-0 Control Board Auxiliary Code U-1 and Later ShutdownOFF Cycle at Shutdown Mechanical Bin Control Activation Sequence Flow Chart Control Board Sequence Flow ChartCycle Bin FullLater Control Board Auxiliary Code U-1Minute Harvest Cycle Freeze Cycle Pump-Out Cycle Fill CycleControl Board Control Board Control Board LayoutPart Number 2A3792-01 High Temperature Safety Harvest Backup Timer and Freeze TimerLow Water Safety Maximum Water Supply Period 6 minutesNo. of Beeps Type of Alarm Every 3 sec LED Lights and Audible Alarm SafetiesSequence Step Energized Time LEDs are On Components Min Max AvgControl Board Auxiliary Code U-1 and Later Default Dip Switch Settings Controls and AdjustmentsHarvest Timer S4 dip switch 1 S4 Dip Switch S4 Dip Switch NoPump-Out Frequency Control S4 dip switch 5 Pump-Out Timer S4 dip switch 3S4 Dip Switch Setting Time seconds Inlet Factory Use S4 dip switch Bin Control Selector/Harvest Pump Timer S4 dip switchControl Board S4 Dip Switch Setting Bin Control Control Board S4 Dip Switch Setting Pump Motor Time secondsFloat Switch Control S5 dip switch 1 G Control Board Freeze Timer S4 dip switch 9Refill Counter S5 dip switch 2 through 5 G Control Board S4 Dip Switch Setting Time MinutesControl Switch Float SwitchBin Control ThermistorWater Pump Switch Discharge Line ModelCooled-AirWater-Cooled Model PressureHigh* Switch Wiring DiagramsKM-901MAH air-cooled and KM-901MWH water-cooled KM-901MRH remote air-cooled PressureSwitchHigh KM-901MRH3 remote air-cooled Cooled-AirModel High* Pressure Switch Cooled-WaterModelHigh Pressure Switch SwitchPressure Performance Data 835 9121480 1570KM-901MRH remote air-cooled KM-901MRH3 remote air-cooled Diagnostic Procedure IV. Service DiagnosisPage OFF Shutdown Thermostatic Bin Control Auxiliary Code T-0, U-0 Control Board CheckControl Correct LED Board Lighting Sequence Bin Control CheckMechanical Bin Control Check Mechanical Bin Control Cleaning Float Switch Check Float Switch Check and CleaningFloat Switch Cleaning Thermistor Check Problem Possible Cause Remedy Diagnostic ChartsNo Ice Production Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Problem Possible Cause Remedy Low Ice Production Abnormal Ice Other Service for Refrigerant Lines Removal and Replacement of ComponentsRefrigerant Recovery Evacuation and Recharge R-404A BrazingRemoval and Replacement of Compressor Removal and Replacement of Expansion Valve Page Removal and Replacement of Evaporator Removal and Replacement of Air-Cooled Condenser Removal and Replacement of Water-Cooled Condenser Removal and Replacement of Remote Air-Cooled Condenser Page Adjustment of Water Regulating Valve water-cooled model Removal and Replacement of Thermistor Removal and Replacement of Inlet Water Valve Removal and Replacement of Pump Motor Removal and Replacement of Control Board Cleaning and Sanitizing Instructions VI. Cleaning and MaintenanceCleaning Procedure Sanitizing Procedure Following Cleaning Procedure Preparing the Icemaker for Long Storage MaintenanceDrain the water tank