5)Attach a compressed air or carbon dioxide supply to the icemaker water supply line drain valve.

6)Move the control switch to the "ICE" position.

7)Replace the front panel in its correct position, then turn on the power supply.

8)Blow the icemaker water supply line out using the compressed air or carbon dioxide supply.

9)Close the icemaker water supply line drain valve.

2.Drain the water tank:

1)Turn off the power supply, then remove the front panel.

2)Move the control switch to the "OFF" position.

3)Remove the base cover, then disconnect one end of the pump tubing to drain the water tank. See Fig. 8. After the water tank has drained, reconnect the pump tubing.

4)Replace the base cover and the front panel in their correct positions.

5)Remove all ice from the storage bin. Clean the storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning.

3.On water-cooled model, remove the water from the water-cooled condenser:

1)Make sure the power supply is off, then remove the front panel and right side panel.

2)Close the condenser water supply line shut-off valve. If connected to a closed loop system, also close the condenser return line shut-off valve.

3)Open the condenser water supply line drain valve. If connected to a closed loop system, also open the condenser return line drain valve.

4)Attach a compressed air or carbon dioxide supply to the condenser water supply line drain valve.

5)Open the water regulating valve by using a screwdriver to pry up on the spring retainer underneath the spring. While holding the valve open, blow out the condenser using the compressed air or carbon dioxide supply until water stops coming out.

6)Close the drain valve(s).

7)Replace the right side panel and front panel in their correct positions.

Disconnect This

End of Pump

Tubing to Drain

Water Tank

Base Cover

Fig. 8

87

Image 87
Contents KM-901MAH KM-901MWH Hoshizaki AMERICA, INC Contents Page Page Unit Important Safety InformationSerious injury Indicates important information about the use and care1a. KM-901MAH air-cooled Auxiliary Code T-0, U-0 Specifications Icemaker1b. KM-901MAH air-cooled Auxiliary Code U-1 and Later Water Cooled Condenser 2a. KM-901MWH water-cooled Auxiliary Code T-0, U-02b. KM-901MWH water-cooled Auxiliary Code U-1 and Later 3a. KM-901MRH remote air-cooled Auxiliary Code T-0, U-0 3b. KM-901MRH remote air-cooled Auxiliary Code U-1 and Later 4a. KM-901MRH3 remote air-cooled Auxiliary Code T-0, U-0 4b. KM-901MRH remote air-cooled Auxiliary Code U-1 and Later Condenser Unit Model URC-9F SpecificationsKM-901MAH air-cooled II. General Information ConstructionKM-901MWH water-cooled KM-901MRH/3 remote air-cooled Sequence of Operation Sequence Cycles and ShutdownControl Board Auxiliary Code T-0, U-0 Control Board Auxiliary Code U-1 and Later ShutdownOFF Cycle at Shutdown Mechanical Bin Control Activation Bin Full Control Board Sequence Flow ChartSequence Flow Chart CycleFill Cycle Control Board Auxiliary Code U-1Later Minute Harvest Cycle Freeze Cycle Pump-Out CycleControl Board Control Board Control Board LayoutPart Number 2A3792-01 Maximum Water Supply Period 6 minutes Harvest Backup Timer and Freeze TimerHigh Temperature Safety Low Water SafetyEnergized Time LEDs are On Components Min Max Avg LED Lights and Audible Alarm SafetiesNo. of Beeps Type of Alarm Every 3 sec Sequence StepControl Board Auxiliary Code U-1 and Later S4 Dip Switch S4 Dip Switch No Controls and AdjustmentsDefault Dip Switch Settings Harvest Timer S4 dip switch 1Pump-Out Timer S4 dip switch 3 Pump-Out Frequency Control S4 dip switch 5S4 Dip Switch Setting Time seconds Inlet Control Board S4 Dip Switch Setting Pump Motor Time seconds Bin Control Selector/Harvest Pump Timer S4 dip switchFactory Use S4 dip switch Control Board S4 Dip Switch Setting Bin ControlS4 Dip Switch Setting Time Minutes Freeze Timer S4 dip switch 9Float Switch Control S5 dip switch 1 G Control Board Refill Counter S5 dip switch 2 through 5 G Control BoardThermistor Float SwitchControl Switch Bin ControlWater Pump Switch Discharge Line Wiring Diagrams ModelCooled-AirWater-Cooled Model PressureHigh* SwitchKM-901MAH air-cooled and KM-901MWH water-cooled PressureSwitch KM-901MRH remote air-cooledHigh KM-901MRH3 remote air-cooled Cooled-AirModel High* Pressure Switch Cooled-WaterModelHigh Pressure Switch SwitchPressure Performance Data 1570 912835 1480KM-901MRH remote air-cooled KM-901MRH3 remote air-cooled Diagnostic Procedure IV. Service DiagnosisPage OFF Shutdown Thermostatic Bin Control Auxiliary Code T-0, U-0 Control Board CheckControl Correct LED Board Lighting Sequence Bin Control CheckMechanical Bin Control Check Mechanical Bin Control Cleaning Float Switch Check Float Switch Check and CleaningFloat Switch Cleaning Thermistor Check Diagnostic Charts Problem Possible Cause RemedyNo Ice Production Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Problem Possible Cause Remedy Low Ice Production Abnormal Ice Other Removal and Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Evacuation and Recharge R-404A BrazingRemoval and Replacement of Compressor Removal and Replacement of Expansion Valve Page Removal and Replacement of Evaporator Removal and Replacement of Air-Cooled Condenser Removal and Replacement of Water-Cooled Condenser Removal and Replacement of Remote Air-Cooled Condenser Page Adjustment of Water Regulating Valve water-cooled model Removal and Replacement of Thermistor Removal and Replacement of Inlet Water Valve Removal and Replacement of Pump Motor Removal and Replacement of Control Board Cleaning and Sanitizing Instructions VI. Cleaning and MaintenanceCleaning Procedure Sanitizing Procedure Following Cleaning Procedure Preparing the Icemaker for Long Storage MaintenanceDrain the water tank