
CME1356R and CME1656R
For The Installer: Remote Condenser
Locate the condenser as near as possible to the  | If the excess tubing is cut out, after   | 
interior location of the ice maker.  | tubing must be evacuated prior to connection to  | 
Note: The location of the condenser relative to the  | the ice maker or condenser.  | 
ice machine is LIMITED by the specification on the  | If the excess tubing is to be coiled, spiral it  | 
following page.  | horizontally to avoid excess trapping in the lines.  | 
  | 
Select the best available location, one that protects Note: A 36" service loop may be placed behind the  | ||
the condenser from extremes of dust, grease and  | ice machine.  | |
sun.  | ||
5. Have the roofing contractor seal the holes in the  | ||
  | ||
Meet all applicable building codes.  | roof per local codes.  | |
Roof Attachment  | 
  | |
Install and attach the remote condenser to the roof  | 
  | |
of the building, using the methods and practices of  | 
  | |
construction that conform to the local building  | 
  | |
codes, including having a roofing contractor secure  | 
  | |
the condenser to the roof.  | ERC411 Remote  | |
Note: If using any other condenser besides the  | Condenser  | |
ERC411, its use must be approved by  | Electrical  | |
Scotsman, and a head pressure control  | ||
Power Supply  | ||
valve must be connected to the  | ||
  | ||
condenser coil. The head pressure  | 
  | |
valve kit number is: RCKCME6  | 
  | |
Precharged Line Routing  | 
  | |
Do not connect the precharged tubing  | 
  | |
until all routing and forming of the tubing  | Coil Excess  | |
is complete. See the Coupling  | Tubing  | |
Horizontally  | ||
Instructions for final connections.  | ||
Within the  | ||
  | ||
1. Each set of   | Building  | |
3 8“ diameter liquid line, and a 12” diameter  | 
  | |
discharge line. Both ends of each line have quick  | 
  | |
connect couplings, the end without access valves  | 
  | |
goes to the ice maker.  | 
  | |
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 2“. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible.
Note: Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
Typical Installation
May 2001
Page 10