Service Diagnosis

Problem or Symptom

Possible Cause

Probable Correction

 

 

 

 

Scale in water system.

Clean water system.

 

 

 

 

Water or Air Temperatures too

Check temps. Unit cannot

 

operate with water and air

 

cold

 

temps below stated limits.

 

 

 

Low system charge

Recover and weigh charge.

 

Bypass solenoid does not open

Check solenoid operation

Poor Harvest

Check valve leaks back

Replace check valve

 

 

 

 

 

 

Check for power to the coil, if

 

Hot gas valve does not open

there is power, replace the hot

 

 

gas valve

 

 

 

 

Head pressure control valve

Replace the head pressure

 

does not maintain enough

 

control valve

 

pressure (in freeze)

 

 

 

 

 

 

High discharge pressure, from a

Clean the condenser, repair the

 

dirty condenser or faulty fan

 

fan motor

 

motor

 

 

 

Extreme hot location

Relocate the cabinet

 

Extremely hot condenser

Move condenser or provide

 

location

shade

 

 

 

 

Overcharge of refrigerant

Recover, evacuate and weigh in

 

the nameplate charge

Low capacity

 

 

 

 

At the end of the freeze cycle,

 

 

 

 

there should be a definite

 

Hot gas valve leaks thru, unit off

difference in temperature

 

on refrigeration error

between the inlet and outlet of

 

 

the Hot Gas Valve. If not,

 

 

replace the hot gas valve

 

Liquid and discharge lines are

Separate and insulate them

 

in contact with each other

 

 

 

 

Low on refrigerant, locate leak,

 

 

recover refrigerant, repair leak,

 

 

replace drier, evacuate and

 

 

weigh in the nameplate charge.

 

 

 

 

 

TXV superheat too high, check

 

 

charge, if charge is OK, replace

Compressor cycles on and off

Compressor overheats

TXV

 

 

Mechanical fault with

 

 

compressor, replace

 

 

compressor

 

 

Internal relief valve opened,

 

 

check for cause of high

 

 

discharge pressure

 

 

 

 

 

 

May 2001

Page 34

Image 34
Contents CME1356R and CME1656R CME1356R and CME1656R CME1356R and CME1656R Condenser and Ice Machine LayoutsPre-Installation Serial Number PlateLocation & Assembly Bin Control Installation Bin Control Mount BulbStacking Kit KSCME6-LG-B Stacking For The Installer Remote Condenser CME1356R and CME1656R Coupling Instructions Tighten Swivel NutHead Pressure Control Add-On Kit Electrical Drain PlumbingSupply Water Filters Follow all applicable codesAfter Utility Connections Final Check ListComponent Location and Function AutoIQ Controller Freeze Cycle Initial Start UpInitial Start 30 seconds Harvest CycleIf there was a problem during Initial Start Up AdjustmentsHow to Adjust the Amount of Water Purge How To Operate The AutoIQ Controller How The Electronic Cuber Works Refrigeration SystemVolt Water SystemHigh Voltage Technicians Only Freeze Cycle Sequence AutoIQ Controller Operation, Beginning freezeWater Light Refrigeration Technicians Only Harvest Cycle Sequence & Other NotesHarvest LightSanitation and Cleaning To Properly Place the Evaporator Covers Additional MaintenanceTo drain reservoir if desired Additional Maintenance Water Distributors Additional Maintenance Inlet Water Valve Screen Additional Maintenance Ice Sensors, Condenser To Clean the Remote Air Cooled CondenserService Diagnosis Diagnostic Light Analysis Problem or Symptom Possible Cause Probable CorrectionService Diagnosis Service Diagnosis Components TXV March Operational Characteristics CME1356R Operational Characteristics CME1656R Removal and Replacement Water Level Sensor/Float Stem Removal and Replacement AutoIQ Controller Removal and Replacement Water Level Sensor Removal and Replacement Refrigerant Liquid Charging Before Calling for Service Check the followingService Bulletin