CME1356R and CME1656R

Operational Characteristics: CME1356R

Cycle Times (Minutes):

 

0oF. condenser air 70oF. indoor

90oF. condenser air 90oF. indoor

 

air, 55oF. water

air, 70oF. water

Freeze

11 ½ - 12 ½

16 - 17

 

 

 

Harvest

3

2 ½

 

 

 

 

 

 

System Pressures (PSIG)

 

70oF. condenser air 70oF. indoor

90oF. condenser air 90oF. indoor

 

air, 55oF. water

air, 70oF. water

Suction: End of Freeze

29 - 31

30

- 32

 

 

 

 

Suction: Peak in Harvest

70 - 80

95

- 105

 

 

 

Discharge: 5 minutes into Freeze

230 - 250

275 - 285

 

 

 

Discharge: Minimum in Harvest

80

100

 

 

 

 

 

 

 

 

Number of Evaporators:

￿5

Refrigerant Charge

￿288 ounces of R-404A

Typical Compressor Amps, single phase

￿freeze 14 - 15

￿harvest 17 - 18

Typical Compressor Amps, three phase

￿freeze 8 - 9

￿harvest 10 - 11

Typical Harvest Ice Weight

￿16.0 lb

Superheat

￿The TXV will control a nominal superheat point that can vary unit to unit from 11oF. to 17oF.

While controlling that point the superheat can also range + or - 4oF. without affecting performance.

Hi Pressure Control - Automatic Reset

￿Hi Pressure Cut Out - 450 PSIG

￿Hi Pressure Cut In - 350 PSIG

Headmaster Valve

￿Setting is 240 PSIG

March 2003

Page 36

Image 36
Contents CME1356R and CME1656R CME1356R and CME1656R CME1356R and CME1656R Condenser and Ice Machine LayoutsPre-Installation Serial Number PlateLocation & Assembly Bin Control Installation Bin Control Mount BulbStacking Kit KSCME6-LG-B Stacking For The Installer Remote Condenser CME1356R and CME1656R Coupling Instructions Tighten Swivel NutHead Pressure Control Add-On Kit Electrical Plumbing SupplyDrain Water Filters Follow all applicable codesAfter Utility Connections Final Check ListComponent Location and Function AutoIQ Controller Initial Start Up Initial Start 30 secondsFreeze Cycle Harvest CycleAdjustments If there was a problem during Initial Start UpHow to Adjust the Amount of Water Purge How To Operate The AutoIQ Controller How The Electronic Cuber Works Refrigeration SystemWater System VoltHigh Voltage Technicians Only Freeze Cycle Sequence AutoIQ Controller Operation, Beginning freezeTechnicians Only Harvest Cycle Sequence & Other Notes HarvestWater Light Refrigeration LightSanitation and Cleaning Additional Maintenance To Properly Place the Evaporator CoversTo drain reservoir if desired Additional Maintenance Water Distributors Additional Maintenance Inlet Water Valve Screen Additional Maintenance Ice Sensors, Condenser To Clean the Remote Air Cooled CondenserService Diagnosis Diagnostic Light Analysis Problem or Symptom Possible Cause Probable CorrectionService Diagnosis Service Diagnosis Components TXV March Operational Characteristics CME1356R Operational Characteristics CME1656R Removal and Replacement Water Level Sensor/Float Stem Removal and Replacement AutoIQ Controller Removal and Replacement Water Level Sensor Removal and Replacement Refrigerant Liquid Charging Before Calling for Service Check the followingService Bulletin