CME1356R and CME1656R
Head Pressure Control Add-On Kit
Kit: RCKCME6GX
Required when a CME1656R or CME1356R is to be connected to a Remote Condenser that is not equipped with a Head Pressure Control Valve
Required Tools: Screwdriver; Drill; 5/32" drill bit; Two Adjustable Wrenches; POE Oil
1.Remove cover from metal box.
2.Locate correct position on condenser: The RCKCME6GX can fit either a Mac G series or a Mac X series condenser.
Use a back up wrench to be certain that the tubing is NOT ROTATING. Only the SWIVEL NUTS should be rotating!
Then use an adjustable wrench to tighten them until no threads are seen AND a very definite resistance is felt.
9.Mark the positions of the swivel nuts to the condenser panel.
10.Rotate the swivel nuts additional
3. Use metal box as a template, mark the positions 11. Place cover on metal box & secure with screws. of 4 holes to be drilled to mount the box to the
condenser.
4. Drill four .157" (#22 or 5/32" bit) dia. holes.
5. Remove plastic covers from the condenser’s quick connects and those to be used to connect to the condenser.
6.Thoroughly clean and lubricate the threads and diaphragms of both the condenser’s and the kit’s quick connects. Use Polyolester oil.
7.Mount the box to the condenser with the screws from the kit.
8.Start the swivel nuts by hand.
G series
Connections to
Central Condenser
Central
Lines from
Ice Machine
X Series
May 2001
Page 13