Scotsman Ice CME1656R, CME1356R specifications Head Pressure Control Add-On Kit

Page 13
RCKCME6GX
12. Finish the balance of the installation. Ice machine’s precharged line sets will now connect to the quick connect fittings on the metal box instead of the condenser’s.

CME1356R and CME1656R

Head Pressure Control Add-On Kit

Kit: RCKCME6GX

Required when a CME1656R or CME1356R is to be connected to a Remote Condenser that is not equipped with a Head Pressure Control Valve

Required Tools: Screwdriver; Drill; 5/32" drill bit; Two Adjustable Wrenches; POE Oil

1.Remove cover from metal box.

2.Locate correct position on condenser: The RCKCME6GX can fit either a Mac G series or a Mac X series condenser.

￿Use a back up wrench to be certain that the tubing is NOT ROTATING. Only the SWIVEL NUTS should be rotating!

￿Then use an adjustable wrench to tighten them until no threads are seen AND a very definite resistance is felt.

9.Mark the positions of the swivel nuts to the condenser panel.

10.Rotate the swivel nuts additional one-quarter turn.

3. Use metal box as a template, mark the positions 11. Place cover on metal box & secure with screws. of 4 holes to be drilled to mount the box to the

condenser.

4. Drill four .157" (#22 or 5/32" bit) dia. holes.

5. Remove plastic covers from the condenser’s quick connects and those to be used to connect to the condenser.

6.Thoroughly clean and lubricate the threads and diaphragms of both the condenser’s and the kit’s quick connects. Use Polyolester oil.

7.Mount the box to the condenser with the screws from the kit.

8.Start the swivel nuts by hand.

G series

Connections to

Central Condenser

Central

Pre-Charged

Lines from

Ice Machine

X Series

May 2001

Page 13

Image 13
Contents CME1356R and CME1656R CME1356R and CME1656R Condenser and Ice Machine Layouts CME1356R and CME1656RSerial Number Plate Pre-InstallationLocation & Assembly Bin Control Installation Mount Bulb Bin ControlStacking Kit KSCME6-LG-B Stacking For The Installer Remote Condenser CME1356R and CME1656R Tighten Swivel Nut Coupling InstructionsHead Pressure Control Add-On Kit Electrical Supply PlumbingDrain Water Filters Follow all applicable codesFinal Check List After Utility ConnectionsComponent Location and Function AutoIQ Controller Initial Start 30 seconds Initial Start UpFreeze Cycle Harvest CycleIf there was a problem during Initial Start Up AdjustmentsHow to Adjust the Amount of Water Purge How To Operate The AutoIQ Controller Refrigeration System How The Electronic Cuber WorksVolt Water SystemHigh Voltage AutoIQ Controller Operation, Beginning freeze Technicians Only Freeze Cycle SequenceHarvest Technicians Only Harvest Cycle Sequence & Other NotesWater Light Refrigeration LightSanitation and Cleaning To Properly Place the Evaporator Covers Additional MaintenanceTo drain reservoir if desired Additional Maintenance Water Distributors Additional Maintenance Inlet Water Valve Screen To Clean the Remote Air Cooled Condenser Additional Maintenance Ice Sensors, CondenserProblem or Symptom Possible Cause Probable Correction Service Diagnosis Diagnostic Light AnalysisService Diagnosis Service Diagnosis Components TXV March Operational Characteristics CME1356R Operational Characteristics CME1656R Removal and Replacement Water Level Sensor/Float Stem Removal and Replacement AutoIQ Controller Removal and Replacement Water Level Sensor Removal and Replacement Refrigerant Liquid Charging Check the following Before Calling for ServiceService Bulletin