Scotsman Ice CME1356R, CME1656R specifications Liquid Charging

Page 44

CME1356R and CME1656R

Liquid Charging

Because R-404A is a near-azeotrope, only liquid refrigerant can be used to recharge the refrigeration system. To do that may take some special techniques:

1.Use an electronic scale to measure the charge.

2.Place a drum or cylinder of R-404A on the scale, valve side up (most R-404A disposable cylinders have an internal dip tube and dispense liquid refrigerant from the valve when it is upright - check yours).

3.A refrigeration manifold should be attached to the service access valves. Attach the charging hose to the cylinder of R-404A. Open the cylinder’s valve and purge the hose to the manifold.

4.Close the low side service access valve.

5.Open the discharge side manifold valve and weigh in the name plate charge. After the charge is weighed in, wait a few minutes and re-check the scale.

6.If all of the refrigerant charge has not been weighed into the discharge side, it must be carefully added thru the low side. Close the discharge service access valve.

7.With a sight glass or charge faster in the hose to the low side port, start the ice machine.

8.Open the low side service access valve.

9.Crack open the low side manifold valve and watch the scale and sight glass. Open and close the low side manifold valve to flow liquid into the manifold but flash off to vapor before it enters the suction side of the refrigeration system. This should only be a few ounces at most.

10.After the scale = the correct charge, shut off the valve on the refrigerant cylinder.

11.With the ice machine running and the discharge access valve closed, open both manifold valves to allow the refrigerant in the hoses to enter the system.

12.Shut the suction service access valve.

13.Remove the refrigeration manifold gages.

14.Replace and tighten all caps.

March 2003

Page 44

Image 44
Contents CME1356R and CME1656R CME1356R and CME1656R CME1356R and CME1656R Condenser and Ice Machine LayoutsPre-Installation Serial Number PlateLocation & Assembly Bin Control Installation Bin Control Mount BulbStacking Kit KSCME6-LG-B Stacking For The Installer Remote Condenser CME1356R and CME1656R Coupling Instructions Tighten Swivel NutHead Pressure Control Add-On Kit Electrical Plumbing SupplyDrain Water Filters Follow all applicable codesAfter Utility Connections Final Check ListComponent Location and Function AutoIQ Controller Initial Start Up Initial Start 30 secondsFreeze Cycle Harvest CycleHow to Adjust the Amount of Water Purge AdjustmentsIf there was a problem during Initial Start Up How To Operate The AutoIQ Controller How The Electronic Cuber Works Refrigeration SystemHigh Voltage Water SystemVolt Technicians Only Freeze Cycle Sequence AutoIQ Controller Operation, Beginning freezeTechnicians Only Harvest Cycle Sequence & Other Notes HarvestWater Light Refrigeration LightSanitation and Cleaning To drain reservoir if desired Additional MaintenanceTo Properly Place the Evaporator Covers Additional Maintenance Water Distributors Additional Maintenance Inlet Water Valve Screen Additional Maintenance Ice Sensors, Condenser To Clean the Remote Air Cooled CondenserService Diagnosis Diagnostic Light Analysis Problem or Symptom Possible Cause Probable CorrectionService Diagnosis Service Diagnosis Components TXV March Operational Characteristics CME1356R Operational Characteristics CME1656R Removal and Replacement Water Level Sensor/Float Stem Removal and Replacement AutoIQ Controller Removal and Replacement Water Level Sensor Removal and Replacement Refrigerant Liquid Charging Before Calling for Service Check the followingService Bulletin