Scotsman Ice specifications CME1356R and CME1656R

Page 11

CME1356R and CME1656R

Remote Condenser Location

Use the following for planning the placement of the condenser relative to the ice machine

Location Limits - condenser location must not exceed ANY of the following limits:

Maximum rise from the ice machine to the condenser is 35 physical feet

Maximum drop from the ice machine to the condenser is 15 physical feet

Physical line set maximum length is 100 feet.

Calculated line set length maximum is 150.

Calculation Formula:

Drop = dd x 6.6 (dd = distance in feet)

Rise = rd x 1.7 (rd = distance in feet)

Horizontal Run = hd x 1 (hd = distance in feet)

Calculation: Drop(s) + Rise(s) + Horizontal Run = dd+rd+hd = Calculated Line Length

Do NOT:

Route a line set that rises, then falls, then rises.

Route a line set that falls, then rises, then falls.

Calculation Example 1:

The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.

5 feet x 6.6 = 33. 33 + 20 = 53. This location would be acceptable

Calculation Example 2:

The condenser is to be located 35 feet above and then 100 feet away horizontally.

35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.

Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.

Operating a machine with an unacceptable configuration will void the refrigeration system warranty.

 

 

40.35"hd

 

Remote

Condenser Distance &

 

Condenser

Location Schematic

 

Located ABOVE

 

 

Ice Machine

 

22.87"

Max 35’

 

rd

 

dd

Max 15’

 

17.15"

 

 

 

Remote

 

 

Condenser

 

 

Located BELOW

 

 

Ice Machine

 

May 2001

Page 11

Image 11
Contents CME1356R and CME1656R CME1356R and CME1656R Condenser and Ice Machine Layouts CME1356R and CME1656RSerial Number Plate Pre-InstallationLocation & Assembly Bin Control Installation Mount Bulb Bin ControlStacking Kit KSCME6-LG-B Stacking For The Installer Remote Condenser CME1356R and CME1656R Tighten Swivel Nut Coupling InstructionsHead Pressure Control Add-On Kit Electrical Water Filters Follow all applicable codes PlumbingSupply DrainFinal Check List After Utility ConnectionsComponent Location and Function AutoIQ Controller Harvest Cycle Initial Start UpInitial Start 30 seconds Freeze CycleHow to Adjust the Amount of Water Purge AdjustmentsIf there was a problem during Initial Start Up How To Operate The AutoIQ Controller Refrigeration System How The Electronic Cuber WorksHigh Voltage Water SystemVolt AutoIQ Controller Operation, Beginning freeze Technicians Only Freeze Cycle SequenceLight Technicians Only Harvest Cycle Sequence & Other NotesHarvest Water Light RefrigerationSanitation and Cleaning To drain reservoir if desired Additional MaintenanceTo Properly Place the Evaporator Covers Additional Maintenance Water Distributors Additional Maintenance Inlet Water Valve Screen To Clean the Remote Air Cooled Condenser Additional Maintenance Ice Sensors, CondenserProblem or Symptom Possible Cause Probable Correction Service Diagnosis Diagnostic Light AnalysisService Diagnosis Service Diagnosis Components TXV March Operational Characteristics CME1356R Operational Characteristics CME1656R Removal and Replacement Water Level Sensor/Float Stem Removal and Replacement AutoIQ Controller Removal and Replacement Water Level Sensor Removal and Replacement Refrigerant Liquid Charging Check the following Before Calling for ServiceService Bulletin