2) Motor 150%-overload time limit



The motor 150%-overload time limit parameter  is used to set the time elapsed before the motor trips under a load of 150% (overload trip ) within a range of 10 to 2400 seconds.

 

 

 

 

[Example: setting of ]

 

 

 

 

 

 

 

 

Monitored output

Motor overload withstanding time [s]

 

 

 

Operation frequency

current [%]

 

(Outline data)

 

 

 

 





=

=

 

 

 

no less than



 

 

Operation frequency

 

=

=

[Hz] [Hz]

Motor overload

0.01

[Hz](*1)

 

68

34

7200

3600

 

 

 

70

35

3600

1800

withstanding time [s]

 

 

 

 

 

 

 

 

80

40

1000

500

 

 

 

 

 

90

45

600

300

 

 

 

 

 

100

50

420

210

 

 

 

 

 

112

56

12000

310

6000

155

 

 

 

 

 

120

60

2400

270

1200

135

 

 

 

 

 

130

65

1200

230

600

115

 

 

 

 

 

140

70

800

190

400

95

 

 

 

 

 

150

75

600

170

300

85

Motor 150%-overload

 

 

 

200

100

270

110

135

55

time limit



 

 

 

 

 

 

 

 

 

 

0

 

×

 

 

Monitored output current [%]

 

 

 

 

 

1.1

 

 

 

 

 

 

 

 

 

 

×1.5

(*1) Except for the cases of

×0.6

 



 

 

 

 

 

,  [Hz]

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

Default setting



Motor 150%-overload time limit

 to  [s]



3) Inverter overload characteristic

This function is provided to protect the inverter itself and it cannot be changed or disabled by changing any parameter setting.

If the inverter overload trip function () is activated frequently, this condition can be improved by changing the setting of the stall prevention level parameter  to a lower level or increasing the acceleration time  or the deceleration time .

Inverter overload withstanding time [s]

small/medium capacity types: 120 large capacity types: 60

Output

Inverter overload withstanding

time

[s]

(Outline

data)

 

current

 

200V:0.455kW

200V:75,90kW

[%]

400V:0.7575kW

400V:90/110280kW

 

111

4800

 

 

2400

 

120

480

 

 

240

 

130

240

 

 

120

 

140

160

 

 

80

 

150

120

 

 

60

 

160

10

 

 

9

 

170

4

 

 

3

 

180

2

 

 

0.3

 

215

0.5

 

 

-

 

110

150

Monitored output current [%]

100%: Inverter's rated output current

If the load applied to the inverter exceeds 150% of its rated load or the operation frequency is less than 0.1Hz, the inverter may trip in a shorter time.

Inverter's overload protective characteristic

E-27

Page 88
Image 88
Toshiba VF-A7 instruction manual Motor 150%-overload time limit , Inverter overload characteristic