■Calorific values of inverters and amount of air to be ventilated

The VF-A7 series of inverter loses about 5% of energy when switching electric currents from AC, DC, then to AC. To limit a temperature rise due to this energy loss, it is necessary to forcefully ventilate and cool down the cabinet in which the inverter is installed.

The table below lists the amounts of air to be ventilated forcefully and the heat radiation areas required for closed-type cabinets containing an inverter.

Voltage

Applicable

Calorific value

Amount of air to be

Heat radiation area

required

motor

of inverter

ventilated forcefully

for closed-type

cabinet

class

(kW)

(W)

(m3/min.)

(m2)

 

 

 

 

0.4

50

0.29

1.0

 

 

0.75

70

0.40

1.4

 

 

1.5

110

0.63

2.2

 

 

2.2

140

0.80

2.8

 

 

3.7

220

1.3

4.4

 

 

5.5

310

1.8

6.2

 

 

7.5

420

2.4

8.4

 

200V

11

580

3.3

11.6

 

15

770

4.4

15.4

 

 

18.5

940

5.4

18.8

 

 

22

1110

6.3

22.2

 

 

30

1490

8.5

29.8

 

 

37

1530

8.7

30.6

 

 

45

1850

10.5

37.0

 

 

55

2250

12.8

45.0

 

 

75

3050

17.4

61.0

 

 

90

3650

20.8

73.0

 

 

0.75

70

0.40

1.4

 

 

1.5

110

0.63

2.2

 

 

2.2

140

0.80

2.8

 

 

3.7

220

1.3

4.4

 

 

5.5

280

1.6

5.6

 

 

7.5

370

2.1

7.4

 

 

11

530

3.0

10.6

 

 

15

710

4.0

14.2

 

 

18.5

800

4.6

16.0

 

400V

22

940

5.4

18.8

 

30

1270

7.2

25.4

 

 

37

1270

7.2

25.4

 

 

45

1490

8.5

29.8

 

 

55

1810

10.3

36.2

 

 

75

2300

13.1

46.0

 

 

90

2750

15.7

55.0

 

 

110

3350

19.1

67.0

 

 

132

4010

22.9

80.2

 

 

160

4850

27.6

97.0

 

 

220

6650

37.9

133.0

 

 

280

8450

48.2

169.0

 

Note)The calorific values in the above table do not include those of optional external devices (such as input reactors, DC reactors and radio noise filters).