■Output terminal function(open collector, relay outputs) settings and detection levels

Technical terms

Alarm:・・・・・・・・・・・・・・ Alarm output beyond a certain setting value

Pre-alarm: ・・・・・・・・・・ Alarm output of the state where the inverter may carry out a trip by continuation

Serious failure: ・・・・・・ Output signal in a serious failure of the protection function of the inverter. (Arm over-current(, , ), Load side over-current(), Short- circuiting(, ), Phase failure(, ), etc.)

Light failure:・・・・・・・・・ Output signal in a slight failure of the protection function of the inverter. (Over-load(, ), Over-voltage(, , ), Over-current(, , , , , ), etc.)

Emergency stop: ・・・・ Output signal when the inverter comes into emergency stop. Stopping manner is set with (emergency stop).

Table of output terminal functions and detection levels

 

Parameter setting

Function

Operation output specifications (in case of positive logic)

 

 

Positive

Negative

 

 

logic

logic

 

 

 

 

 

 

Lower limit frequency

"ON": The running frequency is higher than the setting of 

 

 

0

1

(Lower limit frequency).

 

 

()

"OFF": The running frequency is equal to or lower than the setting

 

 

 

 

 

 

 

 

 

of .

 

 

2

3

Upper limit frequency

"ON": The running frequency is equal to or higher than the setting

 

 

of (Upper limit frequency).

 

 

()

 

 

 

 

"OFF": The running frequency is lower than the setting of .

 

 

 

 

 

 

 

4

5

Low speed signal

"ON": The running frequency is equal to or higher than the setting

 

 

of (low-speed signal output frequency).

 

 

 

 

 

"OFF": The running frequency is lower than the setting of .

 

 

6

7

Acceleration/deceleration

"ON": The difference between the frequency command and the

 

 

completion

running frequency is within the setting of .

 

 

 

 

"OFF": In acceleration or deceleration.

 

 

 

 

 

 

 

 

 

 

"ON": The running frequency is in the range of ±.

 

 

8

9

Specified speed arrival

"OFF": The running frequency is out of the range of

 

 

 

 

 

±.

 

 

10

11

Failure FL (all trip)

"ON": Inverter is tripped.

 

 

"OFF": Inverter trip is cancelled.

 

 

 

 

 

 

 

12

13

Failure FL (except for

"ON": Inverter is tripped (except EF and OCL).

 

 

 and )

"OFF": Inverter trip is cancelled (reset).

 

 

 

 

 

"ON": Inverter output current is over the (Stall prevention

 

 

14

15

Over-current pre-alarm

level) set value.

 

 

 

 

 

"OFF": Inverter output current is under the set value.

 

 

16

17

Inverter overload

"ON": A certain rate of inverter overload() detection time is over.

 

 

pre-alarm

"OFF": The detection time is within a certain limit.

 

 

 

 

 

 

18

19

Motor overload

"ON": A certain rate of motor overload() detection time is over.

 

 

pre-alarm

"OFF": The detection time is within a certain limit.

 

 

 

 

 

 

 

 

 

"ON": The temperature of the cooling fin is 85or higher inside

 

 

20

21

Overheat pre-alarm

the inverter.

 

 

"OFF": The temperature drops to 80or lower after overheat

 

 

 

 

 

 

 

 

 

 

pre-alarm was on.

 

 

22

23

Over-voltage pre-alarm

"ON": In over-voltage control operation or PB operation.

 

 

(200V class: 370 VDC approx., 400V class: 740 VDC approx.)

 

 

 

 

 

 

 

 

 

Main circuit

"ON": The main circuit voltage is lower than the main circuit under-

 

 

24

25

under-voltage ()

voltage detection () level.

 

 

 

 

detected

(200V class: 200 VDC approx., 400V class: 380 VDC approx.)

 

 

 

 

 

"ON": is set at and the state that inverter output current is

 

 

26

27

Low current detected

set value or larger continued more than  set

 

 

 

 

 

value.

 

 

28

29

Over-torque detected

"ON": The state that torque current component is ()

 

 

set value or larger continued more than  set value.

 

 

 

 

 

 

 

30

31

Braking resistor overload

"ON": A certain rate of braking resister overload trip()

 

 

() pre-alarm

detection time is over.

 

 

 

 

 

"OFF": The detection time is within a certain limit.

 

 

32

33

In emergency stop

"ON": In emergency stop operation ("" is indicated).

 

 

"OFF": No emergency stop operation is performed.

 

 

 

 

 

 

 

34

35

In course of retry

"ON": In retry operation ("" is indicated).

 

 

"OFF": No retry operation is performed.

 

 

 

 

 

 

 

36

37

Pattern run switching

"ON": In normal operation or pattern operation has finished.

 

 

output

"OFF": In pattern operation.

 

 

 

 

 

 

 

 

 

 

 