Motor noise reduction

Can be used to suppress the magnetic noise from motor.

filter (for large capacity

 

 

 

 

model only)

 

 

 

 

 

In a system in which 400 V class general motor is driven by a voltage PWM type inverter

 

Motor end surge

using a high-speed switching device (IGBT, etc.), surge voltage depending on cable constant

voltage suppression

may cause deterioration in insulation of motor winding. Take measures against surge voltage

filter

such as use of insulation-reinforced motor, installation of AC reactor, surge voltage

 

(for 400 V models only)

suppression filter, sine wave filter and so on in the inverter’s output side.

 

 

Note) Set the carrier frequency to 2.2kHz when sine wave filter is used.

 

 

For inverters of 22 kW or less models, it is needless to input control power to the terminal

 

 

(RO, SO) because those models are internally supplied with control voltage from the main

 

 

circuit power supply.

 

 

To use the main circuit power supply and control power supply separately for inverters of 22

 

 

kW or less models, use an optional control power supply unit. (Inverters of 30 kW or more

 

 

models have a built-in control power supply circuit respectively.)

 

 

Installation of optional control power supply unit (for 22 kW or less models)

 

 

For installing an optional control power supply unit, remove the jumper connector

 

 

(CN21) inside the inverter and connect the connector of the option to it.

 

 

Install the optional control power supply unit nearby the inverter.

 

 

Outward appearance of option unit

 

 

Name plate

 

 

(Caution label)

 

 

Window for LED and

 

 

hole for cooling

 

 

If this unit is charged

 

 

LED inside this

 

 

window lights.

 

 

Connector (6 pole)

 

 

Connect to the

 

 

inverter.

Control power converter

 

 

 

 

unit

 

 

 

 

 

Cable (70 cm)

 

 

Outside dimensions of optional control power supply unit

 

 

 

Unit: mm

 

(Model: CPS0011) *Common use for 200 V and 400 V models

I-6