6.13.3 Retry function

 Retry selection

Warning

Mandatory

Do not get near the alarm-stopped motor and machine.

When the inverter is in retry mode, the alarm-stopped motor and machine unexpectedly restart when the predetermined time has passed, and thus might cause you to get an injury. Stick caution labels to the inverter, the motor and the machine, to prevent accidents due to an unexpected restart of them because of the retry function.

Function

The inverter automatically resets itself when it has tripped. During a retry, according to the setting of (Auto-restart mode selection) the inverter automatically restarts and this function makes smooth motor activation possible.

[Parameter setting]

 

 

Title

 

Function

 

Adjustment range

 

Default setting

 

 



Retry selection

 

0: Disabled,  times

 

Causes of tripping and retry process

 

 

 

 

 

Cause of tripping

 

Retry process

 

Canceling conditions

 

 

Momentary

a maximum of 10 consecutive retries

Retry is canceled if the inverter

 

 

power failure

1st retry : about 1 [s] after tripping

trips again for reasons other than a

 

 

Over-current

momentary power failure, over-

 

 

Over-voltage

2nd retry: about 2 [s] after tripping

current, over-voltage or overload,

 

 

Overload

3rd retry : about 3 [s] after tripping

or if the inverter fails to restart

 

 

 

 

 

within the predetermined number

 

 

 

 

10th retry : about 10 [s] after tripping

of retries.

Kinds of trips can be retried



Over-current



Overload of inverter



Over heat

Over-current of DC injection



Overload of motor

 

 



Over-voltage



Overload of braking resister

 

No retry is performed if the inverter trips for the following reasons:

,,: Arm short circuit

 : Interruption communication error



: Phase failure(input side)

 : Gate array fault



: Phase failure(output side)

 : Output current detector error



: Loaded side over-current at start time : Optional unit fault

, : Ground-fault

 : Flash memory fault

: Emergency stop

 : Sink/source switching error



: EEPROM error

 : Speed error (Over speed)



: Main RAM error

 : Key error



: Main ROM error

Others (other than the above)



: CPU fault

 

During a retry, the fault detection relay (FLA, B and C) is not active.

A virtual cooling time is set for trips due to an overload (,,). Therefore, a retry is performed after a virtual cooling time and the retry time have passed.

In the case of a trip due to an over-voltage (), the inverter may trips again unless the voltage in its D.C. section falls enough.

In the case of a trip due to overheating (), the inverter may trip again unless the temperature inside it falls enough; the inverter monitors the temperature in it.

A retry is performed if  is set enabled, even if the trip holding selection parameter  is set at .

During a retry,  and the value selected with the status monitor selection parameter  are displayed alternately.

F-24