6.30.2 Using the RS485 port fitted as standard

With the standard serial RS485, you can connect each inverter to a higher-order control system (host computer) to set up a data communications network between inverters. Also, you can establish a data communications link between a computer and each inverter.

Serial RS485 connectors should be used to connect inverters to one another.

Data transfer specification

Item

Specification

Interface

RS485

Transmission path

Half-duplex transmission [2/4-wire, bus architecture (A terminator needs

specification

to be attached at each end of the system.)]

Transmission distance

Up to 500 m (overall length of the cable)

Number of

Up to 32 units (including a host computer)

connectable units

Up to 32

Synchronization mode

Asynchronous transfer

Data transfer rate

Default setting: 9600 bps (parameter setting)

Selectable from among1200, 2400, 4800, 9600, 19200 and 38400 bps

 

Transmission character

ASCII code ... JIS X 0201 8-bit (ASCII)

Binary code ... Binary code, 8-bit fixed

 

Stop-bit length

Received by inverter: 1 bit, sent from inverter: 2 bits

Error detecting system

Parity: even/ odd/ non (parameter setting), check sum

Error correction function

Not provided

Response monitoring

Not provided

Transmission code

Sending: 11 bit, Reception: 12 bit(with parity)

Transmission waiting

Possible

time setting

 

 

Action the inverter takes when an timeout occurs: tripping/alarm/no action

Others

→When alarm is selected, "" blinks at the left end of the control panel.

 

When tripping is selected, "" is displayed on the control panel.

An example of the connection of inverters linked to a computer Selective communications

When an operation frequency reference is isued by the host computer to the inverter No.

Wiring

Host computerData Host→Inverter) :Return dataInverter→Host

 

 

 

〜〜

 

 

INV

 

INV

 

INV

 

INV

 

INV

 

INV

No.00

IG

No.01

IG

No.02

IG

No.03

 

No.29

IG

No.30

IG

(IG)Ignore: Inverters take no action if their numbers do not agree with the number specified in the command( they ignore data received and get ready to receive the next data.)

☆:Use a terminal board, etc., to divide each cable into branches. The host computer transmits data to inverters.

Each inverter receives data from the host computer and checks the number specified by the computer against its number.

Only the inverter with the number that agrees with that specified by the computer decodes the command and takes action according to it.

On completion of the action, the inverter returns the results of the action taken to the host computer, with the inverter number added to this information.

In this case, the inverter No. 3 only operates according to the operation frequency command given by the host computer to it across the network.

F-74

Page 165
Image 165
Toshiba VF-A7 instruction manual Using the RS485 port fitted as standard