J-3

2. Extended parameters

[1] Frequency signal

 

 

Sensorless vector/vector with sensor (●valid, :invalid)

Title

Communi

Function

Adjustment range

Min. unit (panel/

Default

Write during

Vector control

V/f

Reference

Speed

Torque

Position

 

cation No.

 

 

communication)

setting

running

control

control

control

Constant

section



0100

Low-speed signal output frequency

0.0 [Hz]

0.01/0.01

0.0

Enabled

●/●

●/●

/●

6.1.1



0101

Speed reach setting frequency

0.0 [Hz]

0.01/0.01

0.0

Enabled

●/●

●/●

/●

6.1.2



0102

Speed reach detection band

0.0 [Hz]

0.01/0.01

2.5

Enabled

●/●

●/●

/●

6.1.2

[2] Input signal selection

 

 

 

 

 

 

 

 

 

Title

Communi

Function

Adjustment range

Min. unit (panel/

Default

Write during

Vector control

V/f

Reference

Speed

Torque

Position

 

cation No.

 

 

communication)

setting

running

control

control

control

Constant

section



0103

ST (standby) signal selection

0: Standard, 1: Always ON, 2: Interlock with F/R terminal

0

Disabled

●/●

●/●

/●

6.2.1



0105

Priority selection (both F-CC, R-CC are ON)

0: Reverse, 1: Stop

0

Disabled

●/●

●/●

/●

6.2.2



0106

Priority setting of input terminal

0: Disabled, 1: Enabled

0

Disabled

●/●

●/●

/●

6.2.3

 

 

 

0: None

 

 

 

 

 

 

 

 

 

 

 

1: 12-bit binary input

 

 

 

 

 

 

 

 

 

 

 

2: 16-bit binary input

 

 

 

 

 

 

 

 

 

 

Binary/BCD signal selection

3: 3-digit BCD input

 

 

 

 

 

 

 

 



0107

4: 4-digit BCD input

0

Disabled

●/●

●/●

 

 

(Expansion TB option unit)

5: Reverse 12-bit binary input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6: Reverse 16-bit binary input

 

 

 

 

 

 

 

 

 

 

 

7: Reverse 3-digit BCD input

 

 

 

 

 

 

 

 

 

 

 

8: Reverse 4-digit BCD input

 

 

 

 

 

 

 

 



0108

Up-down frequency

07

1/1

0

Disabled

●/●

/

/

[3] Terminal function selection (1/2)

Title

Communi

Function

 

Adjustment range

Min. unit (panel/

Default

Write during

Vector control

V/f

Reference

 

Speed

Torque

Position

 

cation No.

 

 

 

communication)

setting

running

control

control

control

Constant

section



0110

Always active function selection

0135

 

0

Disabled

●/●

●/●

/●

6.3.1



0111

Input terminal selection #1 (F)

0135

 

2(F)

Disabled

●/●

●/●

/●

7.2.1



0112

Input terminal selection #2 (R)

0135

 

4(R)

Disabled

●/●

●/●

/●

7.2.1



0113

Input terminal selection #3 (ST)

0135

 

6(ST)

Disabled

●/●

●/●

/●

7.2.1



0114

Input terminal selection #4 (RES)

0135

 

8(RES)

Disabled

●/●

●/●

/●

7.2.1



0115

Input terminal selection #5 (S1)

0135

 

10(S1)

Disabled

●/●

●/●

/●

7.2.1



0116

Input terminal selection #6 (S2)

0135

 

12(S2)

Disabled

●/●

●/●

/●

7.2.1



0117

Input terminal selection #7 (S3)

0135

 

14(S3)

Disabled

●/●

●/●

/●

7.2.1



0118

Input terminal selection #8 (S4)

0135

 

16(S4)

Disabled

●/●

●/●

/●

7.2.1



0119

Input terminal selection #9 (B8)

0135

 

0

Disabled

●/●

●/●

/●

7.2.1



0120

Input terminal selection #10 (B9)

0135

 

0

Disabled

●/●

●/●

/●

7.2.1

(Reference section): Refer to the inverter's individual manual.