6.25.7 Action at low currents

 Low-current trip

 Low-current detection level

 Low-current detection time

Function

If the current is lower than  level and passes for a time longer than , the inverter trips. When  is set at (tripping disabled), it is necessary to set, with , the time elapsed before the inverter trips after the detection of a small current.

Disabled・・・・・not trip(FL is not active)

Low-current alarm can be output by output terminal selection.

Enabled・・・・・The inverter trips if low-current passes during operation for

the time set with  or over.(FL is active)

Title

Function

Adjustment range

Default setting



Low-current trip

: Disabled, : Enabled



Low-current detection level

 [%]



Low-current detection time

 [s]

6.25.8 Detection of output phase failure

 Detection of output short-circuit during start-up

 Adjustment of detection pulse for output short-circuit during start-up

Function

The function is to detect short circuits with inverter's output terminals.

Title

 

Function

Adjustment range

Default setting

 

Detection of output short-

: Standard

 



: Only one time at power injection or at

circuit during start-up

 

 

 

first start after reset

 

 

Adjustment of detection pulse

 [μs]

 



for output

short-circuit during



 

start-up

 

 

 

 ・・・ : Standard―――detecting at starting

A check is made once at the first start of operation after the power is turned on or the inverter is reset.

 ・・・ Set the pulse length for the detection of short circuits.

Note) Shorten the pulse length if the motor trips in error (OCL) at start-up, especially a high-speed motor.

6.25.9 Over-torque trip

 Over-torque trip

 Over-torque detection level during power running

 Over-torque detection level during regeneration

 Over-torque detection time

Function

If a torque current exceeding the current set with ,  is detected, the inverter trips and the trip message “” is displayed.

F-59