3) Selection of braking resistor option and braking unit

 

braking resistor option

Overload relay(THR)

 

 

 

 

Continuous

Regulatedamperage

Type

Model

Type form

Rating

regenerative

 

braking

(reference)

form

 

 

 

 

allowable

(*4)

 

 

 

 

capacity (*1)

[A]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFA7-2004P2022PL

Installed

120W

- 70Ω

100W

VFA7-2037PL

120W

- 40Ω

120W

 

VFA7-2055PL

PBR3-2055

240W

- 20Ω

96W

VFA7-2075PL

PBR3-2075

440W

- 15Ω

130W

VFA7-2110P

PBR3-2110

660W

- 10Ω

200W

VFA7-2150P2185P

PBR3-2150

880W - 7.5Ω

270W

VFA7-2220P

PBR3-2220

1760W - 3.3Ω

610W

VFA7-2300PN (*2)

 

 

 

 

 

 

VFA7-2370P1N2550P1N (*2)

PBR-222W002

2200W - 2Ω

1000W

VFA7-2750P1N2900P1N (*3)

DGP600W-B1

3.4kW - 1.7Ω

3400W

46

T65J

VFA7-4007PL4037PL

Installed

120W - 150Ω

120W

VFA7-4055PL

PBR3-4055

240W

- 80Ω

96W

VFA7-4075PL

PBR3-4075

440W

- 60Ω

130W

VFA7-4110PL

PBR3-4110

660W

- 40Ω

190W

VFA7-4150PL4185P

PBR3-4150

880W

- 30Ω

270W

VFA7-4220P

PBR3-4220

1760W - 15Ω

540W

VFA7-4300PN (*2)

 

 

 

 

 

 

VFA7-4370P1N4750P1N (*2)

PBR-417W008

1760W - 8Ω

1000W

VFA7-4110KP1N4160KP1N (*3)

DGP600W-B2

7.4kW - 3.7Ω

7400W

44

T65J

VFA7-4220KP1N (*3)

DGP600W-B3

8.7kW - 1.9Ω

8700W

71

T100J

VFA7-4280KP1N (*3)

DGP600W-B4

14kW - 1.4Ω

14000W

110

T115J

(*1) Continuous regenerative braking allowable capacities vary according to the rated capacity and resistance of the resistor for reasons of endurance.

(*2) To use braking resistor, installing a braking resistor drive circuit option is needed.

(*3) To use braking resistor (DGP600 series), installing a braking resistor drive circuit option is needed. And overload relay on this table is needed.

(*4) Type forms of Toshiba Schneider Electric Ltd. products.

4) Connectable braking resistors and their minimum resistances

The table below lists externally-connectable braking resistors and their minimum admissible resistances. Do not connect any braking resistor with a resistance (total resistance) smaller than the minimum resistance admissible for it.

 

Applicable motor

 

200V class

 

 

400V class

 

Standard

minimum

 

Standard

minimum

 

capacity [kW]

 

 

option [Ω]

resistance [Ω]

 

option [Ω]

resistance [Ω]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.4

70

(Installed)

63

 

 

 

0.75

70

(Installed)

63

150

(Installed)

100

 

 

1.5

70

(Installed)

35

150

(Installed)

100

 

 

2.2

70

(Installed)

25

150

(Installed)

67

 

 

3.7

40

(Installed)

17

150

(Installed)

40

 

 

5.5

 

20

10

 

 

80

40

 

 

7.5

 

15

10

 

 

60

40

 

 

11

 

10

10

 

 

40

40

 

 

15

 

7.5

7.5

 

 

30

30

 

 

18.5

 

7.5

5

 

 

30

20

 

 

22

 

3.3

3.3

 

 

15

13.3

 

 

30

 

3.3

3.3

 

 

13.3

13.3

 

 

37

 

2

1.7

 

 

8

6.7

 

 

45

 

2

1.7

 

 

8

6.7

 

 

55

 

2

1.7

 

 

8

5

 

 

75

 

1.7

1.3

 

 

8

3.3

 

 

90

 

1.7

1

 

 

 

110

 

 

 

3.7

2.5

 

 

132

 

 

 

3.7

2.5

 

 

160

 

 

 

3.7

1.3

 

 

220

 

 

 

1.9

1

 

 

280

 

 

 

1.4

1

 

 

 

 

 

 

 

 

 

 

 

F-28

Page 119
Image 119
Toshiba VF-A7 instruction manual Selection of braking resistor option and braking unit, Type