or
: Low speed signal(b-contact)
Set value
: Low speed signal(a-contact)

6. Extended parameters

Speed control mode

Torque control mode

Extended parameters are used for sophisticated operation, fine adjustment and special purposes. Change parameter settings, as required.

Extended parameter list => Refer to Chapter 10.

6.1Frequency signals

6.1.1 Low-speed signal

 Low-speed signal output frequency

Function

When the output frequency exceeds the frequency set with the parameter F100, an ON signal is put out. The function of this parameter is to send a signal for exciting or releasing an electromagnetic brake.

through the open collector terminal OUT1 or OUT2 (24 Vdc - max. 50 mA). (Default setting: OUT 1)

[Parameter setting]

Tytle

Function

Adjustment range

Default setting



Low-speed signal output frequency





Output frequency [Hz]

 

Set frequency

 



 

0

[s]

 

 

Low-speed signal output (Default setting)

 

 

 

ON

 

 

P24-OUT1

 

 

 

OFF

 

 

 

 

 

 

(

Low-speed signal output: Inversion

 

 

 

ON

 

P24-OUT1

 

 

 

OFF )

[Connection diagram (Sink logic)]

 

 

 

 

 

P24

 

 

 

 

 

 

 

 

 

 

 

 

Ry

 

OUT1(or OUT2)

 

 

Output terminal setting

 

 

 

 

 

 

 

 

 

 

The low-speed signal (ON signal) output function has been assigned to the

 

terminal OUT1 by default. To invert output signals, it is necessary to change

 

the setting of the output terminal selection parameter.

 

[Parameter

setting]

 

 

 

 

 

 

Title

 

Function

Adjustment range

 

 



Output terminal selection #1 (OUT1)



Note) To use OUT2 terminal, set the parameter .

F-1

Page 92