[Set value] : VI/II input

Speed commands are entered by means of external signals (terminal VI: 0 to 10 Vdc

or terminal II: 4 to 20 mAdc).

: RR input

Speeds commands are entered by means of external signals (terminal RR: 0 to 10Vdc).

: RX input

Speed commands are entered by means of external signals (terminal RX: 0 to +/-10 Vdc (+/-5 Vdc).

: RX2 control

Speed commands are entered by means of external signals (terminal RX2 (optional):

0to +/-10 Vdc (+/-5 Vdc)).

: Operating panel input enabled

Frequencies are set by pressing the ▲ ▼ key on the control panel or an extended control panel (optional).

: Binary/BCD input

Speed commands are entered from 12/16-bit binary input(optional) or a BCD (optional).

: Communication common serial option

Speed commands are entered from an RS232C device (optional) or terminal board- equipped RS485 device (optional). → Communication number: FA01

: Communication RS485

Speed commands are entered from the RS485 communication device fitted as standard.

Communication number: FA00

: Communication add-on module option

Speed commands are entered from the network communication device TOSLINE-F10M or S20 (optional).

: Up-down frequency

Speed commands are entered by means of up-down frequency signals from the terminal board (refer to 7.2).

: Pulse input

Speed commands are entered by means of pulses (optional).

Note) This function and the vector control with sensor cannot be used at the same time.

The following communication devices are optionally available.

RS232C (Type: RS2001Z)

RS485 (Type: RS4001Z. Up to 64 units can be connected.)

TOSLINE-F10M/TOSLINE-S20

The functions assigned to the following control terminals (contact input: Refer to 7.2.) are always activated regardless of the settings of the control device selection parameter  and the speed command selection parameter .

Reset terminal (assigned to RES by default, enabled only when the invertor trips)

Standby terminal (assigned to ST by default)

Emergency stop terminal

Be sure to put the inverter out of operation before changing the control device selection parameter  or the speed command selection parameter , though no change can be made to them if the inverter is in operation.

Preset speed operation

 : Set this parameter at  (terminal board).

 : Any setting is valid.

E-7

Page 68
Image 68
Toshiba VF-A7 instruction manual Preset speed operation