6.29.7 Selecting a control panel stop pattern

 Panel stop pattern

Function

This parameter is used to select the mode in which the machine is stopped by pressing the STOP key on the control panel when the operation is started by pressing the RUN key.

1)Slowdown stop

The motor stops in the deceleration time set with the parameter (,  or

).

2) Free-run stop

The output of the inverter is cut off. As a result, the motor coasts to a stop. Depending on the load, the motor can keeps rotating for a while before coming to a complete stop.

[Parameter setting]

Title

Function

Adjustment range

Default setting



Panel stop pattern

: Deceleration stop

: Coast stop

 

 

 

6.29.8 Resetting the inverter from the control panel



: Panel reset function

Function

This parameter is used to reset the inverter by control panel operation when it trip s because of a failure, a fault, etc.

■Resetting method

1)Press the Stop key and make sure that  is displayed.

2)Press the Stop key again to reset the inverter.

Note) If the inverter trips because of trouble indicated with the message , , , or , it may take a bit of time for the inverter to be reset.

[Parameter setting]

Title

Function

Adjustment range

Default setting



Panel reset function

: Disabled, : Enabled

6.29.9Selecting a torque limit in control panel operation mode

 Panel torque limit

Function

With this parameter, you can select a torque limit when torque control is exercised by the control panel.

This parameter is valid only when the inverter is in control panel operation mode.

Control panel operation: The mode of operation obtained by setting the torque command selection parameter  at (Panel input).

[Parameter setting]

 

Title

Function

 

Adjustment range

Default setting

 



Panel torque limit

 

, , , 

 

 

 

 

 

 

Refer to

6.22 for details of torque limit setting.

 

 

 

 

 

 

 

 

 

 

F-69

 