About operation

 

Danger

Reference

 

 

 

 

-Do not touch any inverter's terminal when it is energized even if the motor

3.

 

is standstill, or you could get a shock.

3.

 

-Do not operate switches with a wet hand or not put a wet cloth on the

Prohibited

inverter, or you could get a shock.

3.

-Do not get near the alarm-stopped motor when the system is in retry

 

 

mode, or you could get an injury.

 

 

Take safety measures, for example, attaching a cover to the motor, to

 

 

protect persons against accidents when the motor unexpectedly restarts.

6.21

 

-Don't set the motor constant 3 (exciting inductance:) as 1/2 or less

 

value of default setting value. If the motor constant 3 (exciting

 

 

inductance :) is set as extremely small value, the stole prevention

 

 

function

6.25.2

 

will incorrect-operate and will raise output frequency.

 

-Don't set the stole prevention level() as extremely small value.

 

 

When the stole prevention level() is set as motor no-load current

 

 

or value lower than it, the stole prevention function always operates. And

 

 

if it is judged as regeneration mode, frequency will be raised.

 

 

Please do not set the stole prevention level() to 30% or less in

 

 

the usual usage.

 

 

-Do not turn on the power before attaching the front cover. When the

3.

 

inverter is installed in a cabinet with the inverter's front panel detached,

9.

 

always close the door of the cabinet before turning on the power.

 

Mandatory

Turning on the power with the cover or the door left opened could lead to

 

an electric shock.

 

 

 

 

-Turn off the operation signal before resetting the inverter after trouble, or

3.

 

the motor unexpectedly restarts, causing injury to persons.

 

 

 

 

 

Warning

Reference

 

 

 

 

-Operate the motor always within the allowable operation range. (Refer to

 

 

the motor’s instruction manual for the allowable operation range.)

3.

Mandatory

Failure to do so could cause injury to persons.

 

 

 

When selecting the sequence that automatically restarts the motor after

recovery from a momentary power failure (Applicable to inverters)

 

Warning

Reference

 

 

 

 

-Do not get near the motor or the machine.

6.13.1

 

The motor and the machine unexpectedly restart after recovery from a

 

 

momentary power failure.

 

Mandatory

-Stick caution labels to the inverter, the motor and the machine, to prevent

 

accidents due to an unexpected restart of them after recovery from a

 

 

 

 

momentary power failure.

 

5