RX-CC

 

RR-CCVI-CC

 

 

 

Motor torque [%]

 

Motor torque [%]

 

 

 

 

 

100

 

 

100

 

 

 

 

 

-10V

0

 

 

0

 

 

 

 

 

 

 

0V

10V

 

 

 

0V

+10V

 

 

 

 

 

 

 

 

 

 

 

 

 

II-CC

 

 

 

 

 

-100

Motor torque [%]

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

4mA

20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Title

 

Function

 

Adjustment range

Default setting

 

 

 

 

 

: VI(voltage) / II(current)

 

 

 

Selection of power running

: RR(volume / voltage)

 

 



torque

limit #1

: RX(voltage)

 

 

 

 

 

 

 

: RX2(voltage)(optional)

 

 

 

 

 

 

: 

 

 

 

 

 

 

 

 

: VI(voltage) / II(current)

 

 

 

Selection of regenerative

: RR(volume / voltage)

 

 



: RX(voltage)

 

 

 

torque

limit #1

 

 

 

 

 

 

 

: RX2(voltage)(optional)

 

 

 

 

 

 

: 

 

 

 

The torque limit function is active in vector control mode. In V/f constant control mode, square reduction control mode, and V/f 5-point setting mode, the torque limit function plays the same role as the stall preventive function (6.25.2).

In torque control mode, the values set with these parameters limit torque command values.

(2) Positive/negative torque limits

First, you need to set the polarity of each torque limit. Set  at .

Title

Function

Adjustment range

Setting value



Torque limit

: Power running/regenerative torque limit

mode (polarity)

: Positive/negative torque limit

a) Limiting the torque with parameters

Positive

 

 



:

Power running torque limit #1

Regenerative Power running

 

 

Reverse

 

Forward

Power running Regenerative

 

 



:

Regenerative torque limit #1

Negative

 

 

F-47

 

 

Page 138
Image 138
Toshiba VF-A7 instruction manual Positive/negative torque limits,  Torque Limit #1, Limiting the torque with parameters