J-1

1. Basic parameters (1/2)

Vector control
Title Communi
cation No
.
Function Adjustment range Minimum
setup unit
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
Reference
section
 0000 Automatic
acceleration/deceleration
0: Manual acceleration/deceleration
1: Automatic acceleration/deceleration 0 Disabled /5.1
 0001 Automatic V/f mode setting
0: (0 is always displayed.)
1: Automatic torque boost + auto-tuning
2: Sensorless vector control (speed) + auto-tun ing
3: Automatic energy-saving + auto-tuning
0 Disabled /5.2
 0003 Operation command mode
selection
0: Terminal block enabled
1: Operating panel enabled
2: Common serial communication option enabled
3: Serial communication RS485 enabled
4:
Communication add-on cassette option enabled
0 Disabled / / / 5.3
 0004 Speed setting mode
selection
1: VI (voltage input)/II (current input)
2: RR (volume/voltage input)
3: RX (voltage input)
4: RX2 (voltage input) (optional)
5: Operating panel input
6: Binary/BCD input(optional)
7: Common serial communication option(FA01)
8: Serial communication RS485(FA05)
9: Communication add-on cassette option(FA07)
10: Up-down frequency
11: Pulse input #1 (optional)
2 Disabled /5.3
 0005 FM terminal meter
selection 033 0Enabled
/ / / 5.4
 0006 FM terminal meter
adjustment Enabled / / / 5.4
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
/ / /
 0007 Standard setting mode
selection
0:
1: 50Hz standard setting
2: 60Hz standard setting
3: Factory default setting
4: Trip clear
5: Clearing accumulating operation time
6: Initialization of type form information
7: Memorization of user-defined parameters
8: Reset of user-defined parameters
0 Disabled
/ / /
5.5
Sensorless vector/vector with sensor ( valid, :invalid)
10. Table of parameters