If you set in advance the acceleration and deceleration times (,) so that they match the average load condition, you can make the optimum setting to control the motor with a higher accuracy according to changes in the load applied.

[Procedure for setting the automatic acceleration and deceleration times]

Key operated

LED display

Operation

 

 

The running frequency is displayed. (If the monitor display

 



mode setting parameter  is set at [Running

 

 

frequency])

MON



Press the [MON] key to call up the first basic

parameter  (Automatic acceleration/deceleration).

 

 

ENT

Press the Enter key to display the parameter setting.

 

 

 

Change the parameter setting to  (automatic

acceleration/deceleration enabled) by pressing key.

 

 

ENT



Press the Enter key to save the change. Then,  and

the set value are displayed alternately.

 

 

5.1.2 Manually setting the acceleration and deceleration times

This section describes how to set the acceleration time (the operation frequency goes up from 0Hz to the maximum frequency  and the deceleration time (the operation frequency goes down from the maximum frequency  to 0Hz).

Output frequency [Hz]



 

 (Manual setting)

 

Time [s]





[Parameter setting]

Title

Function

Adjustment range

Default setting



Acceleration time #1

 (See

note.)

~

 [s]

Model

dependent



Deceleration time #1

 (See

note.)

~

 [s]

Model

dependent

Note) The minimum setting of acceleration and deceleration times have been set respectively at 0.1sec. by default, but they can be changed within a range of 0.01 to 10 sec. by changing the setting of the parameter  (Acceleration/deceleration time lower limit).

Refer to 6.23.3 for details.

If the acceleration or deceleration time is set shorter than the optimum time, which varies according to the loading condition, it may become longer than the set time because of the over-current stall function or the over-voltage stall function. In addition, if the acceleration or deceleration time is set much shorter, the inverter trips more easily to protect itself from an over-current or an over-voltage.

(Refer to 12.1 for details.)

E-2

Page 63
Image 63
Toshiba VF-A7 Manually setting the acceleration and deceleration times, Change the parameter setting to  automatic