Jump frequency band #2

6.10Jump frequency - Jumping resonant frequencies

 Jump frequency #1

 Jump frequency band #1

 Jump frequency #2

 Jump frequency band #2

 Jump frequency #3

 Jump frequency band #3

Function

These parameters are used to jump resonant frequencies to avoid resonance with the natural frequency of the mechanical equipment operated. In jump mode, the motor exhibits hysteresis with respect to the jump frequency.

Output frequency [Hz]

Jump frequency #1()

Jump frequency #2()

Jump frequency #3()

[Parameter setting]

Jump frequency band #1 ()

Jump frequency band #2



Jump frequency band #3 

Setting frequency

Title

Function

Adjustment range

Default setting



Jump frequency #1







Jump frequency band #1







Jump frequency #2







Jump frequency band #2







Jump frequency #3







Jump frequency band #3





If the upper limit frequency () is within a jump frequency range, it is limited to the lowest frequency in the jump frequency range.

If the lower limit frequency () is within a jump frequency range, it is limited to the highest frequency in the jump frequency range.

Do not overlap upper limit freqency () and lower limit frequency () within a jump frequency range. If they are overlapped,it is operated lowest jump frequency.

Do not overlap two or more jump frequency ranges,or it cannot be operated within normal range.

The operation frequency is not jumped during acceleration or deceleration.





Jump frequency band #1

6.11 Preset-speed #815



 Preset-speed #8#15

Refer to 5.14 for details.