9.Selection of peripheral devices

Danger

When using the inverter without the front cover, be sure to place the inverter unit inside a

Mandatory

cabinet. If they are used outside the cabinet, it may cause electric shock.

Be sure to ground every unit. If not, it may cause electric shock or fire on the occasion of

Be grounded

failure, short-circuit or electric leak.

 

9. 1 Selection of wiring equipment

Voltage

class

Applicable motor [kW]

Inverter model

Wire size AWGcross-section [mm2]

Main circuit(*1) DC reactor Braking resistor Earth cable

(optional) (optional)

 

 

0.4

VFA7-2004PL

 

 

 

 

 

 

 

0.75

VFA7-2007PL

 

14(2)

 

 

 

 

 

1.5

VFA7-2015PL

14(2)

14(2) (*5)

12(3.5)

 

 

 

 

 

2.2

VFA7-2022PL

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

VFA7-2037PL

 

12(3.5)

 

 

 

 

 

5.5

VFA7-2055PL

12(3.5)

10(5.5)

 

 

 

 

 

7.5

VFA7-2075PL

10(5.5)

8(8)

10(5.5)

10(5.5)

 

200V

11

VFA7-2110P

6(14)

6(14)

6(14)

 

 

 

 

15

VFA7-2150P

4(22)

 

 

 

class

 

 

 

 

 

18.5

VFA7-2185P

4(22)

2(38)

8(8)

4(22)

 

 

 

 

22

VFA7-2220P

2(38)

6(14)

 

 

 

 

 

 

30

VFA7-2300P

2/0(60)

2/0(60)

2(38)

 

 

 

 

 

 

37

VFA7-2370P1

4/0(100)

4(22)

 

 

 

 

 

 

45

VFA7-2450P1

4/0(100)

300

2/0(60)

 

 

55

VFA7-2550P1

 

 

 

 

 

(150)

 

 

 

 

 

75

VFA7-2750P1

300(150)

2(38) or

4/0(100)

 

 

 

 

 

90

VFA7-2900P1

400(200)

6×2(14×2)

 

 

 

 

 

 

0.75

VFA7-4007PL

 

 

 

 

 

 

 

1.5

VFA7-4015PL

 

 

14(2)

(*5)

 

 

 

2.2

VFA7-4022PL

14(2)

14(2)

 

 

 

 

 

 

 

 

3.7

VFA7-4037PL

 

 

 

12(3.5)

 

 

 

 

 

 

 

 

5.5

VFA7-4055PL

 

 

 

 

 

 

 

7.5

VFA7-4075PL

 

12(3.5)

14(2)

 

 

 

11

VFA7-4110PL

12(3.5)

10(5.5)

 

 

 

 

 

 

 

 

15

VFA7-4150PL

10(5.5)

8(8)

 

 

10(5.5)

 

 

18.5

VFA7-4185P

8(8)

6(14)

 

 

8(8)

 

400V

22

VFA7-4220P

6(14)

10(5.5)

6(14)

 

 

 

30

VFA7-4300P

4(22)

 

 

 

 

 

 

 

 

class

 

 

 

 

 

 

 

 

37

VFA7-4370P1

4(22)

2(38)

 

 

 

 

 

45

VFA7-4450P1

2(38)

6(14)

4(22)

 

 

 

 

 

55

VFA7-4550P1

2/0(60)

 

 

 

 

 

 

 

 

 

75

VFA7-4750P1

2/0(60)

4/0(100)

 

 

2(38)

 

 

90/110

VFA7-4110KP1

4/0(100)

 

 

2/0(60)

 

 

132

VFA7-4132KP1

 

4(22)

 

 

 

 

 

 

 

160

VFA7-4160KP1

300(150)

300(150)

 

 

4/0(100)

 

 

220

VFA7-4220KP1

400(200)

300×2

2/0(60) or

 

 

(150×2)

4×2(22×2)

 

 

 

 

 

 

 

 

 

280

VFA7-4280KP1

300×2

400×2

4/0(100) or

300

 

 

(150×2)

(200×2)

2/0×2(60×2)

(150)

 

 

 

 

 

(*1): Indicates

wire sizes

of input terminals R, S, T and output terminals U, V, W. Wiring distance is supposed to

be 30 m at maximum.

(*2): The recommended cable size is that of the cable (e.g. 600V class,HIV cable) with continuous maximum permissible temperature of 75°C.

(*3): For the control circuit, use shielded wires whose size (cross-section) is 0.75 mm2 or more. The size (cross- section) of wires supplying control power is 2.0 mm2 or more.

(*4): For the earth cable, use wires larger than the specified ones in size (cross-section). (UL standard)

(*5): Recommended wire size for external braking resistor. Refer to 6.13.4 for use of external braking resistor.

(*6): Do not connect more than two wires to a terminal block (except for terminal blocks of 2900, 4160K to 4280K and PA terminals of models that have only one PA terminal). If wiring with more than two wires is needed, set a external relay terminal.