7. 3. 1 Setup by analog input signals (RR terminal)

If a variable resistor (1-10 kΩ, 1/4 W) for setting up frequency is connected with the RR terminal, the inverter can be run and stopped with external commands.

For bringing this function into practice, connect a potentiometer to the terminals of PP, RR and

CCso as to divide the reference voltage (10 VDC) at the terminal PP and to input 0 to 10 VDC of divided voltage between the RR and CC terminals.

If analog voltage signal of 0 to 10 VDC is input between the terminals of RR and CC, frequency can be set up without connection of a potentiometer.

<Related parameters>

Title

Function

Adjustment range



Operation command mode selection



Speed setting mode selection





FM terminal meter selection





FM terminal meter adjustment



Reference priority selection



Analog input filter

(Disabled) to

 (Max. filter capacity)

 

 



RR reference point #1

 [%]



RR reference point #1 frequency

 [Hz]



RR reference point #2

 [%]



RR reference point #2 frequency

 [Hz]



RR reference point #1 rate

 [%]



RR reference point #2 rate

 [%]

Default value

Setup value

(Terminal)

(Terminal)

(RR)

(RR)

 

 

()

()

 

 

 

 





 

 









 

 

 

 





 

 

 

 

 

Run/stop setup

 

 

MCCB

CHARGE

 

Motor

To control switching between forward

 

 

 

 

rotation (F) and reverse rotation (R),

 

R/L1

VF-A7

U/T1

 

Power

IM

run and stop by external commands.

S/L2

 

V/T2

supply

 

Setup of frequency setting signal and

 

T/L3

 

W/T3

 

 

 

 

 

 

running frequency characteristic

 

 

 

RES

 

To set up frequency setting signal to be

 

 

 

S1

 

input to the potentiometer (RR terminal)

 

 

 

 

and characteristic of running frequency.

 

 

 

S2

 

Frequency characteristic is set up at

 

FLA

 

S3

 

the two points of RR reference point #1

 

FLB

 

 

()/frequency(), RR

 

 

S4

 

reference point #2()/frequency

 

 

 

 

 

FLC

FL

 

 

().

 

 

 

 

ST

 

Connection and calibration of

 

 

 

 

 

 

 

F

Forward rotation

frequency meter

 

 

P24

 

Connect a 1 mADC full-scale DC

 

 

 

 

 

 

R

Reverse rotation

current meter, 7.5 VDC full-scale DC

 

 

 

 

OUT1

 

 

 

voltmeter or rectifier type AC voltmeter.

 

 

 

 

For calibration of the meter, refer to the

 

 

 

FM

Frequency

section 5.4.

 

 

 

OUT2

 

 

meter

 

 

 

 

 

 

AM

 

[Hz]

 

 

 

 

 

FP



 

Point 2

 

 

 

 

Running frequency

Point 1

 

 

CC

RX VI II RR PP

 

 

 

 

G/E

 

CC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 



 

[%]

 

 

 

 

 



 

 

 

 

 

 

 



 

 

 

1~10kΩ-1/4W

0%

 

100%

 

 

 

 

 

 

 

 

 

 

 

(0V

10V)

Frequency setting signal