Toshiba VF-A7 instruction manual Presence or absence of parameter trip can be selected

Models: VF-A7

1 250
Download 250 pages 39.4 Kb
Page 240
Image 240

(Continued from the preceding page)

Indication

Contents

Expected causes

Countermeasures

 

 

Input voltage (main circuit)

Check input voltage.

 

 

becomes insufficient in operation.

If undervoltage is detected, set

(*1)

Under-voltage

Momentary power failure occurs

 (regenerative power ride-



(main circuit)

because undervoltage continues

through control),  (auto-restart)

longer than under-voltage

and  (under-voltage detection

 

 

 

 

detection time .

time) as countermeasures against

 

 

 

future momentary power failure.

 

 

Input voltage (control circuit)

Check input voltage.

 

 

becomes insufficient in operation.

If undervoltage is detected, set

(*1)

Under-voltage

Momentary power failure occurs

 (regenerative power ride-



(control circuit)

because undervoltage continues

through control),  (auto-restart)

longer than under-voltage

and  (under-voltage detection

 

 

 

 

detection time .

time) as countermeasures against

 

 

 

future momentary power failure.

(*1)

Over-torque

Load torque reaches over-torque

Check the system if there is



detection level in operation.

something abnormal in it or not.

 



Ground-fault

Output cable or motor falls into

Check units and connections if there



ground-fault.

is ground-fault or not.

 

 

Check settings of to 

parameters for motor.

 

 

Motor whose capacity is smaller by two or more ranks than that of inverter

 

Auto-tuning

is used, isn't it?

 



Extremely think cable is used as inverter output cable, isn't it?

 

error

Motor is running, isn't it?

 

 

 

Motor other than three-phase inductive type is used, isn't it?

 

 

If  error occurs as power is turned on, set motor type parameter as

 

 

 =  (others).

 



Inverter type

Is control board (or drive board of

When board has been replaced, input

 

error

main circuit) replaced?

 for .

 

 

Sink/source switch of

Check connections and set proper

 

 

input/output terminal is set wrong

logic.

 

 

(reversely switched on/off).

After making sure that sequence is

 

Sink/source

 

normal, proceed in operation.



 

If the same error does not occur when

 

switching error

 

the power is turned on again, the

 

 

 

system has recovered normal status.

 

 

 

(Check control terminals and

 

 

 

sink/source switches including those

 

 

 

of add-on options.)

 

 

The signal from a system is not

Please check if the sequence is

 

 

inputted into input terminals.

normal or not.

 

 

The input terminal function (

Please set or  as the input



Sequence error

or ) is not set up.

terminal to use.

For not using the system-

Please set up 0.0, when you do not

 

 

supporting sequence 

use system-supporting sequence.

 

 

function, it is set up except 0.0 at

 

 

 

.

 



Encoder error

Disconnection of encoder circuit.

Check connection of encoder.

 

 

 

Connect encoder correctly.



Speed error

Something abnormal in encoder

Check connection of encoder.

 

(Over speed)

(inverter)

Connect encoder correctly.

 

To much

Potential deviation exceeded the

Check connection of encoder.

 

 set value during position

Increase the setting value of .



potential

control.

Adjust the parameters on position

 

deviation

 

 

control

 

 

 

 

Key error

RUN or STOP key is depressed

Check operation panel.



for 5 seconds or more.

 

 

 

Key is faulty.

 



VI/II input error

Breaking down of a wire for VI/II

Check VI/II input signal

 

 

input signal.

 



 

Connection between the inverter

Check connection between the inverter



 

and optional add-on cassettes is

and optional add-on cassettes. If it is

Read-error

abnormal.

not reset, make a service call.

 

Something abnormal in control

Make a service call.



 

signal.

 

Presence or absence of parameter trip can be selected.

(Note) Please contact us if you find any trips other than the above.