(Continued from the preceding page)

Indication

Contents

Expected causes

Countermeasures

 

 

Input voltage (main circuit)

Check input voltage.

 

 

becomes insufficient in operation.

If undervoltage is detected, set

(*1)

Under-voltage

Momentary power failure occurs

 (regenerative power ride-



(main circuit)

because undervoltage continues

through control),  (auto-restart)

longer than under-voltage

and  (under-voltage detection

 

 

 

 

detection time .

time) as countermeasures against

 

 

 

future momentary power failure.

 

 

Input voltage (control circuit)

Check input voltage.

 

 

becomes insufficient in operation.

If undervoltage is detected, set

(*1)

Under-voltage

Momentary power failure occurs

 (regenerative power ride-



(control circuit)

because undervoltage continues

through control),  (auto-restart)

longer than under-voltage

and  (under-voltage detection

 

 

 

 

detection time .

time) as countermeasures against

 

 

 

future momentary power failure.

(*1)

Over-torque

Load torque reaches over-torque

Check the system if there is



detection level in operation.

something abnormal in it or not.

 



Ground-fault

Output cable or motor falls into

Check units and connections if there



ground-fault.

is ground-fault or not.

 

 

Check settings of to 

parameters for motor.

 

 

Motor whose capacity is smaller by two or more ranks than that of inverter

 

Auto-tuning

is used, isn't it?

 



Extremely think cable is used as inverter output cable, isn't it?

 

error

Motor is running, isn't it?

 

 

 

Motor other than three-phase inductive type is used, isn't it?

 

 

If  error occurs as power is turned on, set motor type parameter as

 

 

 =  (others).

 



Inverter type

Is control board (or drive board of

When board has been replaced, input

 

error

main circuit) replaced?

 for .

 

 

Sink/source switch of

Check connections and set proper

 

 

input/output terminal is set wrong

logic.

 

 

(reversely switched on/off).

After making sure that sequence is

 

Sink/source

 

normal, proceed in operation.



 

If the same error does not occur when

 

switching error

 

the power is turned on again, the

 

 

 

system has recovered normal status.

 

 

 

(Check control terminals and

 

 

 

sink/source switches including those

 

 

 

of add-on options.)

 

 

The signal from a system is not

Please check if the sequence is

 

 

inputted into input terminals.

normal or not.

 

 

The input terminal function (

Please set or  as the input



Sequence error

or ) is not set up.

terminal to use.

For not using the system-

Please set up 0.0, when you do not

 

 

supporting sequence 

use system-supporting sequence.

 

 

function, it is set up except 0.0 at

 

 

 

.

 



Encoder error

Disconnection of encoder circuit.

Check connection of encoder.

 

 

 

Connect encoder correctly.



Speed error

Something abnormal in encoder

Check connection of encoder.

 

(Over speed)

(inverter)

Connect encoder correctly.

 

To much

Potential deviation exceeded the

Check connection of encoder.

 

 set value during position

Increase the setting value of .



potential

control.

Adjust the parameters on position

 

deviation

 

 

control

 

 

 

 

Key error

RUN or STOP key is depressed

Check operation panel.



for 5 seconds or more.

 

 

 

Key is faulty.

 



VI/II input error

Breaking down of a wire for VI/II

Check VI/II input signal

 

 

input signal.

 



 

Connection between the inverter

Check connection between the inverter



 

and optional add-on cassettes is

and optional add-on cassettes. If it is

Read-error

abnormal.

not reset, make a service call.

 

Something abnormal in control

Make a service call.



 

signal.

 

Presence or absence of parameter trip can be selected.

(Note) Please contact us if you find any trips other than the above.