Toshiba VF-A7 Indication Contents Expected causes Countermeasures, ・ Raise carrier frequency 

Models: VF-A7

1 250
Download 250 pages 39.4 Kb
Page 238
Image 238

12.Prior to service callTrip information and countermeasures

12.1 Cause of trip, warning indication (in detail and countermeasures)

If there is something abnormal in the inverter or system, troubleshoot referring to the following table before calling service. If the inverter needs to replace some part or the cause of the trouble cannot be removed by the measures mentioned in the table, consult the dealer of the inverter about the trouble.

[Trip information]

Indication

Contents

Expected causes

 

 

Countermeasures

 

 

Acceleration time #1 is too short.

Extend acceleration time #1 .

 

 

V/f parameter is improperly set.

Check V/f parameter.

 

Overcurrent

Running motor is started during

Use (Auto-restart) or 

 

momentary power failure.

(Regenerative power ride-through control).



during

Special motor (low impedance) is

Raise carrier frequency .



acceleration

used, isn't it?

 

 

 

 

 

(DC current)

 

 

 

 

 

Manual torque boost value() is large.

Decrease setting value.

 

 

 

 

Output cable or motor falls into

Check units and connections if there is

 

 

ground-fault.

ground-fault or not.

 

Overcurrent

Deceleration time #1  is too

Extend deceleration time #1 .

 

short (in deceleration).

 

 

 

 



during

Running motor is started during

Use  (Auto-restart) or  (Regen



deceleration

momentary power failure.

erative power ride-through control).

 

(DC current)

Output cable or motor falls into

Check units and connections if there is

 

 

ground-fault.

ground-fault or not.

 

Overcurrent

Load rapidly varied.

Reduce load variation.



during

Load is abnormal.

Check loading unit.



fixed speed

Output cable or motor falls into

Check units and connections if there is

 

(DC current)

ground-fault.

ground-fault or not.

Note: ,,

A device of main circuit is faulty.

Make a service call.

 originate

Overheat protection is activated.

Check operation of cooling fan.

from causes other

(5.5 to 15 kW, 30 kW or more)

Check cooling fan control mode parameter

than those

Control voltage drop prevention function is

.

 

 

mentioned above.

activated. (5.5 to 15 kW, 30 kW or more)

 

 

 

 

 

Overcurrent

Failure in wiring of main output

Check the wiring and motor insulation.



(loaded side

circuit or motor insulation.

Properly set output short-circuit detection

 

over-current at

Motor impedance is too low.

parameter and .

 

start time)

 

 

 

 

 



U-phase arm

Something abnormal in some

Make

a

service

call.

short-circuit

device of main circuit (U-phase).



V-phase arm

Something abnormal in some

Make

a

service

call.

short-circuit

device of main circuit (V-phase).



W-phase arm

Something abnormal in some

Make

a

service

call.

short-circuit

device of main circuit (W-phase).



Phase failure

Phase lacking in input side of

Check connection of main input circuit for

 

(input side)

main circuit.

phase lacking in input side.

(*1)

Phase failure

Phase lacking in output side of

Check connection of main output circuit and

main circuit.

motor for phase lacking in output side.



(output side)

 

Select output phase failure detection parameter

 

 

 

for checking.

 

 

Input voltage abnormally varied.

Try to insert input reactor.

 

Overvoltage

1: Power-factor improving capacitor was

 

 

 

 

 

turned on/off.

 

 

 

 



during

2: Some unit using thyrister is connected

 

 

 

 

 

acceleration

with the same power supply line.

 

 

 

 

 

 

Running motor is started during

Use (Auto-restart) and 

 

 

momentary power failure status.

(Regenerative power ride-through control).

 

 

Deceleration time #1 is too short

Extend deceleration time #1 .

 

 

(too much regenerated energy).

Install dynamic braking resistor.

 

 

PBR resistance is too high.

Decrease dynamic braking resistance.

 

 

Dynamic braking mode is disabled.

(Also reset the .)

 

Overvoltage

Over-voltage stall protection is

Set dynamic braking mode parameter 



during

disabled.

properly.

 

 

 

deceleration

Input voltage abnormally varied.

Set over-voltage stall protection 

 

 

1 Power-factor improving capacitor was

properly.

 

 

 

 

turned on/off.

Try to insert input reactor.

 

 

2 Some unit using thyrister is connected

 

 

 

 

 

 

with the same power supply line.

 

 

 

 

(*1): Presence or absence of parameter trip can be selected. (Continued on the following page)

L-1