2)An external braking resistor (optional)

a)External braking resistor (with a thermal fuse) (optional)

 

 

 

External braking

resistor

 

 

 

(optional)

 

 

MCCB

PA

PB

 

 

 

Motor

 

 

Power

 

IM

supply

 

 

 

 

 

 

 

Inverter

 

/

[Parameter

setting]

 

 

Title

Function

Adjustment range

Setting value



Dynamic braking

: Disabled

mode selection

: Enabled/overload detection enabled

In the case that the internal dynamic resistor is used in 3.7kW model or less, then do not use any external braking resistors. When using an external braking resistor instead of the internal resistor, change the connection of the internal resistor from terminal PB1 to terminal PR1. (For boosting braking force)

Do not connect an external resistor with a resistance (combined resistance) smaller than the minimum admissible resistance.

For overload protection, be sure to set the parameters  and  properly.

[Parameter

setting]

 

 

 

 

 

 

 

 

 

 

 

Title

 

 

 

Function

 

 

 

 

Adjustment range

Setting value

 



 

Dynamic braking resistance

 

 

 [Ω]

Any value

 



 

Dynamic braking resistor capacity

 

 

 [kW]

 

 

 

 

 

[Externally connectable braking resistors (resistance)]

 

 

 

Voltage

 

Applicable motor

 

Internal braking

 

 

Minimum admissible resistance

 

 

class [V]

 

capacity [kW]

 

resistor

 

 

connected externally [Ω]

 

 

 

 

0.4,

0.75

 

120[W] - 70[Ω]

 

63

 

 

 

200

 

1.5

 

 

 

 

35

 

 

 

 

2.2

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.7

 

 

 

120[W] - 40[Ω]

 

17

 

 

 

400

 

0.75,

1.5

 

120[W] - 150[Ω]

 

100

 

 

 

 

2.2

 

 

 

 

67

 

 

 

 

 

3.7

 

 

 

 

 

 

 

 

40

 

 

F-26