3.2 Simple operation of the VF-A7 [1] [Speed control mode]

A speed control mode can be selected from among three: control panel operation, terminal board operation and combination of both. (Refer to 5.3 for other modes of operation.)

[Terminal operation] : Operation by means of external signals

[Panel operation] :Operation by means of keys on the control panel

[Panel + terminal operation] : Frequency, start and stop signals can be sent individually from the control panel and the terminal board.

3.2.1Operation from the terminal(external signals)

Terminal operation

■Start/Stop

Operation command mode selection [Default setting]

 

and

 

CC

closed : Forward run

To make the motor coast to a stop (coast

 

 

 

 

 

 

 

 

stop),described on the left, break the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection between ST and CC when the

 

 

 

 

 

 

 

 

 

and

 

CC

open : Slowdown stop

motor is out of operation. Then,  is

 

 

 

 

 

 

 

 

displayed on the LED display of the

 

 

 

 

 

 

 

 

inverter rotating speed,

 

 

 

 

 

 

 

 

(When terminals

ST

and

CC

are electrically

 

 

Coast stop

connected.

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

Slowdown stop

speed

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F-CC

ON

Terminal F-CC

 

 

 

 

ON

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

ST-CC

ON

 

 

 

 

 

ON

 

 

Terminal ST-CC

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

■Example of typical connection

 

 

 

MCCB

 

 

 

 

 

Motor

 

Power

 

 

R/L1

 

U/T1

 

IM

 

 

 

S/L2

 

V/T2

 

 

supply

 

 

T/L3

 

W/T3

 

 

 

 

 

 

 

 

 

F

 

Forward run if ON

 

 

 

 

 

 

 

Deceleration stop if OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

Reverse run if ON,

 

 

 

 

 

 

 

 

Slowdown stop if OFF

 

 

 

 

 

Control panel

ST

 

Stand-by if ON,

 

 

 

 

 

 

 

 

free-run stop if OFF

 

 

 

G/E

 

CC

 

 

 

 

 

 

CC

RX VI RR PP

I I

 

Current signal420mAdc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage signal-10+10Vdc

 

 

 

 

 

 

 

 

Voltage signal010Vdc

 

 

 

 

External potentiometer

(or

voltage signal RR-CC: 0

to 10V)

C-3

Page 41
Image 41
Toshiba instruction manual Simple operation of the VF-A7 1 Speed control mode, Example of typical connection