7. 3. 2 Setup by analog input signals (VI/II terminal)

Connect current signal (4 to 20 mADC) to the terminal II or voltage signal (0 to 10 VDC) to the terminal VI so that the inverter can be run and stopped with external commands.

<Related parameters>

Title

Function

Adjustment range



Operation command mode selection



Speed setting mode selection





FM terminal meter selection





FM terminal meter adjustment



Reference priority selection



VI/II reference point #1

 [%]



VI/II reference point #1 frequency

 [Hz]



VI/II reference point #2

 [%]



VI/II reference point #2 frequency

 [Hz]



VI/II reference point #1 rate

 [%]



VI/II reference point #2 rate

 [%]



Analog input filter

(Disabled) to

 (Max. filter capacity)

 

 

Default value (Terminal) (RR)

()    



Setup value

(Terminal)

(VI/II)

()









: Set "" when current signal (4 to 20 mADC) is connected to the terminal II, or set "" when voltage signal (0 to 10 VDC) is connected to the terminal VI.

Power supply

 

 

 

 

■Run/stop setup

 

MCCB

CHARGE

 

Motor

 

To control switching between forward

 

 

 

 

rotation (F) and reverse rotation (R),

R/L1

VF-A7

U/T1

 

 

IM

 

run and stop by external commands.

S/L2

 

V/T2

 

 

■Setup of frequency setting signal and

T/L3

 

W/T3

 

 

 

 

 

 

running frequency characteristic

 

 

RES

 

 

To set up frequency setting signal and

 

 

 

 

characteristic of running frequency that

 

 

 

 

 

 

 

S1

 

 

are to be externally input to the terminal

 

 

S2

 

 

VI or II.

 

 

FLA

 

 

 

Frequency characteristic is set up at

 

 

 

 

 

S3

 

 

the two points of VI/II reference point #1

FLB

 

 

 

 

S4

 

 

()/frequency(), VI/II

 

FL

 

 

reference point #2() /frequency

 

 

 

 

FLC

 

 

 

().

 

 

 

ST

 

 

 

 

 

 

 

■Connection and calibration of

P24

 

F

Forward rotation

 

frequency meter

 

 

R

Reverse rotation

 

Connect a 1 mAdc full-scale DC current

 

 

 

meter, 7.5 V dc full-scale DC voltmeter

OUT1

 

 

 

 

or rectifier type AC voltmeter. For

 

 

FM

Frequency

calibration of the meter, refer to the

OUT2

 

section 5.4.

 

 

 

 

meter

 

[Hz]

 

 

 

 

 

AM

 

 

 

 

 

 

 

FP



 

 

Point 2

 

 

Running frequency

 

 

Point 1

 

 

 

 

 

 

 

 

G/E

 

CC

 

 

 

 

 

 

 

 

 

 

 

 

CC

RX VI II RR PP

 

 

 

 

 

 

 



 

 

[%]

 

 

*0~10Vd

 

 



 

 

 

 

 

 

 



 

 

 

 

0%

20%

 

100%

 

 

 

 

 

 

 

 

 

 

(0

4

20mA)II terminal

 

 

*4~20mAdc

 

(0

 

10V )VI terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency setting signal

The terminals VI and II cannot be used together at a time. Be sure to use either of them.

G-12

Page 179
Image 179