Warning

Prohibited

Do not connect any device or unit with a built-in capacitor (noise filter, surge suppressor, etc.) to output terminals (on the motor side), or it could cause the risk of a fire.

■Prevention of radio noise

Prevent interference, such as radio noise, separately install and bind cables connected to the power supply-side terminals (R/L1, S/L2 and T/L3) of the main circuit and those connected to the motor-side terminals (U/T1, V/T2 and W/T3).

■Power supply to the control and main circuits (for the 22kW and smaller models)

You want to keep the control circuit alive when the main circuit shuts off because of trouble or tripping, you can use an optional power supply unit to supply power to the control circuit separately from the main circuit.

■Notes on wiring

When connecting wires to the main circuit terminals, use crimp contacts because there is no large space between terminals, and attach them in order so that they do not come into contact with each other.

Be sure to ground the inverter by connecting wires of the following size or larger to the grounding terminal G/E.(UL standard)

Voltage

Applicable motor

Grounding wire size

class

AWG(cross-section[mm2])

 

 

0.45.5kW

12(3.5)

 

7.5kW

10(5.5)

 

1115kW

6(14)

200V

18.522kW

4(22)

 

3037kW

2(38)

 

4555kW

2/0(60)

 

7590kW

4/0(100)

 

0.7511kW

12(3.5)

 

15kW

10(5.5)

 

18.5kW

8(8)

 

2230kW

6(14)

400V

3755kW

4(22)

 

75kW

2(38)

 

110132kW

2/0(60)

 

160220kW

4/0(100)

 

280kW

300(150)

For the 200V 0.4~7.5kW models and the 400V 0.75~7.5kW models, a grounding screw (M5) is provided in the wiring hole cover, in addition to a grounding terminal.

Refer to the table in 9.1 for wire sizes.

Wire sizes listed in 9.1 is for the case the wire length is below 30m. To use wires longer than 30m, you need larger cables than listed in 9.1.

Tighten a terminal stand screw with specified bolting torque.

Recommended bolting torque for terminal stand

 

 

Nm

lbins

 

 

M3

0.5

4.4

 

 

M4

1.2

11

 

 

M5

2.4

21

 

 

M6

4.0

35

 

 

M8

8.0

71

 

 

M10

16

142

 

 

M12

32

283

 

 

 

 

 

 

 

 