Basic operating

Step

Setting

Parameter

 

1

Set the pattern run selection parameter at

 (Disabled),

 (Enabled).

 (Enabled)

 

Change all frequencies required to preset-

(Preset-speed #1 to #7)

2

speed frequencies.

(Preset-speed #8 to #15)

 

(Preset-speed operation mode)

 

 

(Preset-speed #1 to #15 control

 

 

 

mode)

 

Set the required operation time at each of

(Preset-speed #1 to #15

3

the set operation frequencies.

 

operation continuation mode)

 

(Preset-speed #1 to #15

 

 

 

 

 

operation time)

 

Set the sequence of each speed

 

 

 

This sequence following three methods.

 

 

 

Select a run/stop operation from the

(Patterned operation canceled during stop)

 

pattern run mode

Pattern run is reset by stop/switching

 

 

operation before operating restarts.

 

 

(Patterned operation continued during stop)

 

 

Pattern run is started by stop/switching

 

 

operation. The system stops temporarily on

 

 

completion of every routine, then proceeds to

 

 

the next routine.

 

Select a pattern group, and then set the

(Cycle number of pattern group #1)

 

sequence of each speed

(Pattern group #1 selection #1 to #8)

4

 

(Cycle number of pattern group #2)

 

(Pattern group #2 selection #1 to #8)

 

 

 

 

(Cycle number of pattern group #3)

 

 

(Pattern group #3 selection #1 to #8)

 

 

(Cycle number of pattern group #4)

 

 

(Pattern group #4 selection #1 to #8)

 

According to the required parameter



 

 

group, select pattern group #1, #2, #3 or

, (Pattern group #1)

 

#4 from input terminal selection  to

 

 

. If you set  at  at

,

(Pattern group #2)

 

 

 

item 3 above, select step trigger signals

,

(Pattern group #3)

 

 

 

from . Selecting pattern

,

(Pattern group #4)

 

 

 

run continuation signals makes it possible

, (Pattern run continuation signal)

 

 

 

to select a start/stop method.

,

(Pattern run trigger signal)

 

 

 

5

Monitor displayed during pattern run

During pattern operation, the following run information is displayed before the normal display.

Condition

Display

Meaning

Pattern group and pattern



(A): Number or the pattern group

(A)(B)

(B): Number of the pattern

 

Number of repetitions



Means that the current pattern operation is to

 

 

be repeated (ex. 123 times).

Preset operation speed



Frequency reference with preset-speed #1

data.

 

 

Remaining time of the



Current pattern is finished in 1234 seconds.



Operation time is set for infinity or the system

current pattern operation

 

is waiting for the next step command.

 

 

■Pattern run switching output (output terminal function : 36, 37)

If the pattern run switching output function is selected (activated), a signal is put out on completion of all the predetermined patterns of operation. When there is no operation command left to be entered or the pattern operation selection signal changes, the output terminals are turned off(in case of a-contact).

Terminal

Title

Function

Adjustment range

Default setting

OUT1

 

Output terminal

 

(pattern run switching output: a-contact





or

 

 

selection #1

 

(pattern run switching output: b-contact

 

 

 

 

Note) To put out the signals to the terminal OUT2, select the parameter .

F-55

Page 146
Image 146
Toshiba VF-A7 instruction manual <Basic operating>, Monitor displayed during pattern run,   ~