Parameter setting

Function

Operation output specifications (in case of positive logic)

Positive

Negative

logic

logic

 

 

38

39

PID deviation limit

"ON": PID deviation is in  or set value.

40

41

Run/stop

"ON": Running frequency is output or DC injection breaking ()

is performed.

 

 

 

 

 

 

"ON": Serious failure(refer to technical terms on the previous page)

42

43

Serious failure

is detected.

"OFF": Inverter has recovered from serious failure. (Serious failure

 

 

 

 

 

 

has been reset)

 

 

 

"ON": Light failure (refer to technical terms on the previous page) is

44

45

Light failure

detected.

"OFF": Inverter has recovered from light failure. (Light failure has

 

 

 

 

 

 

been reset)

 

 

Commercial/INV

 

46

47

switching output #1

Refer to 6.16.

(for inverter operation

 

 

 

 

 

output)

 

 

 

Commercial/INV

 

48

49

switching output #2

Refer to 6.16.

(for commercial

 

 

 

 

 

operation output)

 

50

51

Cooling fan ON/OFF

"ON": Cooling fan is in operation.

"OFF": Cooling fan is off operation.

 

 

 

52

53

In Jog run

"ON": In jog run.

"OFF": In normal operation.

 

 

 

54

55

Panel operation/terminal

"ON": In operation by terminal board.

board operation

"OFF": In operation by control panel.

 

 

switching

 

 

 

56

57

Cumulative operation

"ON": Cumulative operation time is beyond the set value.

time alarm

"OFF": Cumulative operation time is less than the  set value.

 

 

58

59

Abnormal communication

"ON": Communication error caused by scanning has occurred.

alarm #1

"OFF": Communication error is cancelled (reset).

 

 

(caused by scanning)

 

 

 

60

61

Forward/reverse

"OFF": In forward operation.

"ON": In reverse operation.

switching

 

 

(The last status is held while operation is suspended.)

 

 

 

 

 

 

"ON": In operable status or operation can be started with frequency

62

63

Ready for operation #1

command input as an operation switching answer-back.

 

 

 

"OFF": In inoperable status.

 

 

 

"ON": In operable status or operation can be started with ST and

64

65

Ready for operation #2

RUN signals and frequency command input

 

 

 

"OFF": In inoperable status.

66

67

Poor control power supply

"ON": Control circuit under-voltage is detected ().

() pre-alarm

(detection level; 200V class: approx. 145 VAC or lower,

 

 

 

400V class: approx. 290 VAC or lower)

68

69

System consistent

Output the braking signal according to the brake sequence.

sequence

 

 

(BR: Brake release)

 

 

 

 

"ON": More than one of alarm, pre-alarm, under-voltage, low

 

 

 

current over-torque, poor control power supply, PID deviation

70

71

In (pre-)alarm status

limit, abnormal frequency setting or torque limit have occurred

 

 

 

or detected.

 

 

 

"OFF": All the alarms above are cancelled.

72

73

Forward speed limit

"ON": Forward operation speed is  set value or over.

(torque control)

"OFF": Forward operation speed is less than set value.

 

 

74

75

Reverse speed limit

"ON": Reverse operation speed is set value or over.

(torque control)

"OFF": Reverse operation speed is less than  set value.

 

 

76

77

Inverter healthy output

"ON" and "OFF" are alternately output at intervals of 1 second.

 

 

Abnormal communication

"ON": Communication error caused by RS485 logic or message

78

79

alarm #2 (caused by

transmission has occurred.

RS485 logic or

 

 

"OFF": Communication error is cancelled (reset).

 

 

message transmission)

 

 

 

80

81

Error code output #1

 

82

83

Error code output #2

 

84

85

Error code output #3

Output the failure code in 6bits.

86

87

Error code output #4

 

88

89

Error code output #5

 

90

91

Error code output #6

 

G-7

Page 174
Image 174
Toshiba VF-A7 instruction manual Or detected, OFF All the alarms above are cancelled