Toshiba VF-A7 ・ Raise rating of the inverter, ・ Reset the inverter, Stop,  Initial read-error

Models: VF-A7

1 250
Download 250 pages 39.4 Kb
Page 239
Image 239

(Continued from the preceding page)

Indication

Contents

Expected causes

Countermeasures

 

 

Input voltage abnormally varied.

Try to insert input reactor.

 

 

1 Power capacity is 500 kVA or

 

 

 

more.

 

 

 

2 Power-factor improving

 

 

Over-voltage

capacitor was turned on/off.

 

 

3 Some unit using thyrister is

 



during fixed

connected with the same

Install dynamic braking resistor.

 

speed

power supply line.

 

 

 

Motor falls into regeneration status

 

 

 

because it is rotated fast

 

 

 

exceeding inverter's output

 

 

 

frequency by power of loaded

 

 

 

side.

 

 

 

Rapid acceleration is operated.

Extend acceleration time #1 .

 

 

DC breaking rate is too high.

Decrease values of DC injection

 

Inverter

V/f parameter is improperly set.

braking current  and DC



Running motor is started during

injection braking time .

 

overloaded

momentary power failure status

Check V/f parameter.

 

 

or so.

Use (Auto-restart) and 

 

 

Load is too heavy.

(Regenerative power ride-through control).

 

 

 

Raise rating of the inverter.

 

 

V/f parameter is improperly set.

Check V/f parameter.

 

Motor

Motor is locked.

Check loading unit.



Continuous operation in low

Reset  properly to motor's

overloaded

 

 

speed range.

overload reduction start-up

 

 

Motor is operated with overload.

frequency.

 

 

Rapid deceleration is operated.

Extend deceleration time #1 .

 

Dynamic braking

Dynamic braking rate is too high.

Increase capacity (wattage) of



resistor overload

Set over-voltage limit operation

dynamic braking resistor and reset

 

 

the PBR capacity parameter .

 

 

revel parameter  too small.

Increase the setting value of .

 

 

Cooling fan is not actuated.

After cooling down inverter, reset it

 

 

Ambient temperature is too high.

from failure and try to restart it.

 

 

If cooling fan does not work in

 

Overheat

Vent of cooling fan is shut.

operation, it needs replacement.



Secure spaces in the periphery of the

 

 

Some heat generating matter is

inverter.

 

 

located nearby.

Don't locate any heat generating thing

 

 

Internal thermistor of unit is

near the inverter.

 

 

disconnected.

Make a service call.

Emergency

Inverter is stopped by panel operation

Reset the inverter.

stop

during automatic or remote operation.

 

 

 



EEPROM error

Error occurs during writing data.

Again turn on the inverter. If it is not

 

 

 

reset, make a service call.



Initial read-error

Something abnormal in internal data.

Make a service call.



Initial read-error

Something abnormal in internal data.

Make a service call.



Main RAM fault

Something abnormal in control RAM.

Make a service call.



Main ROM fault

Something abnormal in control ROM.

Make a service call.



CPU fault

Something abnormal in control CPU.

Make a service call.

 

Interruption

Something abnormal occurred

Check communication units and their



communication

during communication operation.

connections.

 

fault

 

 



Gate array

Main gate array is abnormal.

Make a service call.

 

fault

 

 



Output current

Main output current detector is

Make a service call.

 

detector error

abnormal.

 

 

Optional unit

Something abnormal occurred in

Check connection of optional



some optional unit (including

board(s).

 

fault

abnormal communication [optional

Refer to instructions of options

 

 

add-on cassettes]).

concerned.



Flush memory

Something abnormal in flush

Make a service call.

 

fault

memory.

 

 

 

Output current declined to the

Check to see if low-current detection

 

low-current

low-current detection level during

level is set properly to the system or

(*1)

operation.

not ().

operation

 

 

 

If low-current detection level is

 

 

 

properly set, make a service call.

(Continued on the following page)

L-2

Page 239
Image 239
Toshiba VF-A7 ・ Raise rating of the inverter, ・ Reset the inverter, Stop,  Initial read-error,  Main RAM fault