J-2

1. Basic parameters (2/2)
Vector control
Title Communi
cation No
.
Function Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
Reference
section
 0008 Forward/reverse selection
(At panel control only)
0: Forward,
1: Reverse 0Enabled
/ / / 5.6
 0009 Acceleration time #1 0.1()6000 [s] 0.01/0.01* See J-28 Enabled /5.1.2
 0010 Deceleration time #1 0.1()6000 [s] 0.01/0.01* See J-28 Enabled /5.1.2
 0011 Maximum frequency 30.0 400.0 [ Hz] 0.01/0.01 80 Disabled / / / 5.7
 0012 Upper limit frequency 0.0  [Hz] 0.01/0.01 80 Enabled /5.8
 0013 Lower limit frequency 0.0  [Hz] 0.01/0.01 0.0 Enabled /5.8
 0014 Base frequency #1 25.0 400.0 [Hz] 0.01/0.01 60 Enabled / / / 5.9
 0015 Motor control mode
selection
0: Constant torque
1: Variable torque mode
2: Automatic torque boost
3: Sensorless vector control (speed)
4:
Automatic torque boost + automatic energy-saving
5:
Sensorless vector control (speed) + automatic energy-saving
6: V/f 5-points setting
7:
Sensorless vector control (speed/torque switching)
8:
PG feedback vector control (speed/torque switching)
9:
PG feedback vector control (speed/position switching)
0 Disabled 5.10
 0016 Manual torque boost 030% 0.1/0.01 See J-28 Enabled 5.12
Setting
Type
Overload
protection Overload stall
0
protect not stall
1
protect stall
2
not protect not stall
3
Standard
motor
not protect stall
4
protect not stall
5
protect stall
6
not protect not stall
 0017
Selection of electronic
thermal protection
characteristics
7
VF motor
(special
motor) not protect stall
0 Disabled / / / 5.13
 0018 Preset-speed #1   [Hz] 0.01/0.01 0.0 Enabled /
 0019 Preset-speed #2   [Hz] 0.01/0.01 0.0 Enabled /
 0020 Preset-speed #3   [Hz] 0.01/0.01 0.0 Enabled /
 0021 Preset-speed #4   [Hz] 0.01/0.01 0.0 Enabled /
 0022 Preset-speed #5   [Hz] 0.01/0.01 0.0 Enabled /
 0023 Preset-speed #6   [Hz] 0.01/0.01 0.0 Enabled /
 0024 Preset-speed #7   [Hz] 0.01/0.01 0.0 Enabled /
5.14


Extended parameter Setting of extended parameters listed on the
following pages / / / 4.1.2
 Automatic edit function To search parameters different from default value / / / 4.1.3
* Minimum setup unit is 0.1 in case of 16-bit access. Sensorless vector/vector with sensor (:valid, :invalid)