13.Regular inspection and maintenance

Danger

Mandatory

Be sure to inspect the inverter regularly.

If the inverter is used without regular inspection, it may cause trouble or accident because sign of disorder or failure is missed.

Complete the following steps before proceeding to inspection. 1 Cut off power supply (turn off the inverter).

2 10 minutes or more after power cutoff, check to see if the charge indicator lamp is turned off.

3 Make sure that voltage in the DC main circuit (between PA and PC) is 45 V or lower by use of a tester capable of measuring high DC tension (800 V DC or more).

If the above-mentioned steps are skipped before inspection, it may cause an electricshock.

To prevent the inverter from failure caused by operating environment such as influence of temperature, humidity, dust and so on, vibration, and aging of component parts, and end of estimated service life, execute daily or regular inspection without fail.

13.1 Regular inspection

Since electronic parts are easily affected by heat, install the inverter in a cool, well-ventilated, dust-free place for making it demonstrate its original performance for a long time.

Purpose of regular inspection is to find sign of failure or malfunction by comparing current data on operation with recorded data on past operation.

Subject of

 

 

Gist of inspection

Criteria of judgment

inspection

Inspection item

Inspection cycle

Inspection method

 

 

1)

Dust,

 

1) Eye-check,

1) Improve bad points.

 

 

humidity, gas

 

thermometer,

2) Pay heed to trace left of

1. Indoor

2)

Dropping of

 

sense of smell

water drop.

 

water and

 

2) Eye-check

3) Maximum 40°C (50°C inside

environment

 

 

 

other liquid

 

3) Thermometer

cabinet)

 

 

 

 

3) Room

 

 

 

 

 

temperature

 

 

 

2. Component

 

 

As occasion

 

If something feels abnormal, open the

 

 

By feel (touch) of

door and check transformer, reactor,

1)

Vibration,

demands

parts and

outside of the

contactor, relay, cooling fan, etc.

 

noise

 

units

 

 

board

Stop the inverter as occasion

 

 

 

 

 

 

 

 

demands.

 

1)

Load current

 

Moving-iron type

Within the rating

3. Operation

2)

Voltage*

 

AC ammeter

Little difference from data on

data (output

3)

Temperature

 

Rectifier type AC

normal status

side)

 

 

 

voltmeter

 

 

 

 

 

Thermometer

 

*)Voltage is differently read depending on the measuring instrument used. Use the same tester or voltmeter for every inspection and record measurement result each time.

■Check points

1.Something unusual in the installation environment

2.Something unusual in the cooling system

3.Unusual vibration and noise

4.Overheat, discoloration

5.Unusual smell

6.Unusual motor vibration, noise and overheat

M-1

Page 245
Image 245
Toshiba VF-A7 Regular inspection, Check points, Inspection method, By feel touch, Vibration Demands Parts Outside