Step 3: Set the property of Auto-restart

1)Case =

[Parameter setting]

Title

Function

Adjustment range

Default setting



Auto-restart adjustment #1



Model dependent



Auto-restart adjustment #2



Model dependent

Example of setting) In the case adjustment value is , set at  and check the property. Notice that in this case, waiting time for the restart grows to 110120[%]. If it cannot be adjusted at setting , , reset the range of  (motor constant #2)at 20~30% lower.

2)Case =

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

: Fast(0.5[s])(with a small inertia application)

 



Auto-restart

: Normal(1.0[s])

Model

adjustment #3

: 1.54.5[s]

dependent

 

 

: Slow(5.0[s])

 

This parameter adjusts the rising time of motor torque at time of restarting. Adjust this parameter to inertia moment of the load.

6.13.2 Regenerative power ride-through control / Deceleration stop

 Regenerative power ride-through control / Deceleration stop

 Ride-through time / Deceleration time

Function

1) Regenerative power ride-through control

When instant electric power failure occurs during operation, this function makes operation continue using the regeneration energy from a motor.

2)Deceleration stop

When instant electric power failure occurs during operation, this function stops the motor quickly compulsorily. A forcible stop is carried out in (Deceleration time) using the regeneration energy from the motor. (Deceleration time changes with control.) After a compulsive stop, it maintains a stop state until operation instruction is once turned off.

[When power is shut off]

 

Input voltage

 

 

 

 

 

 

The time for which the motor keeps running

 

 

 

 

 

 

 

varies with the inertial of the machine operated

 

Motor speed

 

 

 

 

 

free run time

 

and the loading conditions. So, conduct a test

 

 

 

 

 

 

 

to determine the time before using this function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using this function in conjunction with the retry

 

 

 

 

 

 

 

 

 

 

 

function enables the inverter to restart without

 

 

 

 

 

 

 

 

 

About 100[ms]

making a fault stop.

 

 

 

 

 

 

 

 

 

 

The power ride-through control ( = ) is

 

 

 

 

 

 

 

 

 

[]

 

exercised for about 100 [ms]. (A inverter which

 

[When power fails momentarily]

 

 

 

Applicable Motor capacity is 22kW or less is

 

Input voltage

 

 

 

 

 

 

able to continue to control the motor a few

 

 

 

 

 

 

 

seconds.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor speed

 

 

 

 

 

Less than 100[ms] []

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Parameter setting]

 

 

 

 

 

 

 

 

 

Title

 

 

 

Function

 

Adjustment range

Default setting

 

 

 

 

 

 

 

 

 

 

: OFF

 

 



Regenerative power ride-through

: ON (Regenerative

 

 

control / Deceleration stop

 

power ride-through control)

 

 

 

 

 

 

 

 

 

 

 

: ON (Deceleration stop)

 

 



Ride-through time / Deceleration time

 [s]



Note) Even if these functions are used, a motor may free run according to load conditions. In this case, please use the auto restart function together.

Note) These functions do not operate at the time of torque control or position control. Note) Usual slowdown time comes at the time of notes =  and =.

F-23

Page 114
Image 114
Toshiba VF-A7 Regenerative power ride-through control / Deceleration stop, Set the property of Auto-restart, Case =