J-5

[5] Basic parameters #2

 

 

Sensorless vector/vector with sensor (●valid, :invalid)

Title

Communi

Function

Adjustment range

Min. unit (panel/

Default

Write during

Vector control

V/f

Reference

Speed

Torque

Position

 

cation No

 

 

communication)

setting

running

control

control

control

Constant

section



0170

Base frequency #2

25.0400.0 [Hz]

0.01/0.01

60.0

Enabled

6.4.1



0171

Base frequency voltage #2

0.0600.0 [V]

0.1/0.1

See J-28

Enabled

6.4.1



0172

Manual torque boost #2

0.030.0 [%]

0.1/0.01

See J-28

Enabled

6.4.1



0173

Motor overload protection level #2

10100 [%]

1/0.01

100.0

Enabled

6.4.1



0174

Base frequency #3

25.0400.0 [Hz]

0.01/0.01

60.0

Enabled

6.4.1



0175

Base frequency voltage #3

0.0600.0 [V]

0.1/0.1

See J-28

Enabled

6.4.1



0176

Manual torque boost #3

0.030.0 [%]

0.1/0.01

See J-28

Enabled

6.4.1



0177

Motor overload protection level #3

10100 [%]

1/0.01

100

Enabled

6.4.1



0178

Base frequency #4

25.0400.0 [Hz]

0.01/0.01

60.0

Enabled

6.4.1



0179

Base frequency voltage #4

0.0600.0 [V]

0.1/0.1

See J-28

Enabled

6.4.1



0180

Manual torque boost #4

0.030.0 [%]

0.1/0.01

See J-28

Enabled

6.4.1



0181

Motor overload protection level #4

10100 [%]

1/0.01

100

Enabled

6.4.1



0182

Motor switching mode selection

0: standard, 1: customized

-

0

Disabled

●/●

●/●

/●



0183

V/f adjustment coefficient

0255

1/1

32

Enabled

[6] V/f

5-point

setting

 

 

 

 

 

 

 

 

 

Title

Communi

Function

Adjustment range

Min. unit (panel/

Default

Write during

Vector control

V/f

Reference

Speed

Torque

Position

 

cation No

 

 

communication)

setting

running

control

control

control

Constant

section



0190

V/f 5-point setting VF1 frequency

0400 [Hz]

1/1

0

Disabled

6.5



0191

V/f 5-point setting VF1 voltage

0100 [%]

0.1/0.01

0.0

Disabled

6.5



0192

V/f 5-point setting VF2 frequency

0400 [Hz]

1/1

0

Disabled

6.5



0193

V/f 5-point setting VF2 voltage

0100 [%]

0.1/0.01

0.0

Disabled

6.5



0194

V/f 5-point setting VF3 frequency

0400 [Hz]

1/1

0

Disabled

6.5



0195

V/f 5-point setting VF3 voltage

0100 [%]

0.1/0.01

0.0

Disabled

6.5



0196

V/f 5-point setting VF4 frequency

0400 [Hz]

1/1

0

Disabled

6.5



0197

V/f 5-point setting VF4 voltage

0100 [%]

0.1/0.01

0.0

Disabled

6.5



0198

V/f 5-point setting VF5 frequency

0400 [Hz]

1/1

0

Disabled

6.5



0199

V/f 5-point setting VF5 voltage

0100 [%]

0.1/0.01

0.0

Disabled

6.5

(Reference section): Refer to the inverter's individual manual.

Page 207
Image 207
Toshiba VF-A7 instruction manual Basic parameters #2, Point Setting