J-11

[20] Vector control

 

 

 

Sensorless vector/vector with sensor (●valid, :invalid)

Title

Communi

Function

Adjustment range

Min. unit (panel/

Default

 

Write during

Vector control

V/f

Reference

 

Speed

Torque

Position

 

cation No

 

 

communication)

setting

 

running

control

control

control

Constant

section



0374

Current control proportional gain

1.01000

0.1/0.1

209.1

 

Disabled

●/●

●/●

/●



0375

Current control integral gain

1.01250

0.1/0.1

See J-28

 

Disabled

●/●

●/●

/●



0376

Speed loop proportional gain

3.21000

0.1/0.1

See J-28

 

Enabled

●/●

/●



0377

Speed loop integral gain

0.1200. 0 [rad/s]

0.1/0.1

See J-28

 

Enabled

●/●

/●



0378

Motor counter data selection

05

0

 

Disabled

/

/●



0379

Speed loop parameter ratio

0.0110.00 [s]

0.01/0.01

1.00

 

Disabled

●/●

/●

[21]

Preset-speed operation mode

 

 

 

 

 

 

 

 

 

 

Title

Communi

Function

Adjustment range

Min. unit (panel/

Default

 

Write during

Vector control

V/f

Reference

 

Speed

Torque

Position

 

cation No

 

 

communication)

setting

 

running

control

control

control

Constant

section



0380

Preset-speed operation

0: Non-mode preset speed

0

 

Disabled

●/●

5.14

mode

1: Preset speed by mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Forward run

 

 

 

 

 

 

 

 

 

 

 

 

+1: Reverse run

 

 

 

 

 

 

 

 

 

 

 

 

+2: Selection of acc/dec switching #1

 

 

 

 

 

 

 

 

 



0381

Preset-speed #1 control mode

+4: Selection of acc/dec switching #2

0

 

Disabled

●/●

5.14

 

 

 

+8: Selection of V/f switching #1

 

 

 

 

 

 

 

 

 

 

 

 

+16: Selection of V/f switching #2

 

 

 

 

 

 

 

 

 

 

 

 

+32: Selection of torque limit switching #1

 

 

 

 

 

 

 

 

 

 

 

 

+64: Selection of torque limit switching #2

 

 

 

 

 

 

 

 

 



0382

Preset-speed #2 control mode

Ditto

0

 

Disabled

●/●

5.14



0383

Preset-speed #3 control mode

Ditto

0

 

Disabled

●/●

5.14



0384

Preset-speed #4 control mode

Ditto

0

 

Disabled

●/●

5.14



0385

Preset-speed #5 control mode

Ditto

0

 

Disabled

●/●

5.14



0386

Preset-speed #6 control mode

Ditto

0

 

Disabled

●/●

5.14



0387

Preset-speed #7 control mode

Ditto

0

 

Disabled

●/●

5.14



0388

Preset-speed #8 control mode

Ditto

0

 

Disabled

●/●

5.14



0389

Preset-speed #9 control mode

Ditto

0

 

Disabled

●/●

5.14



0390

Preset-speed #10 control mode

Ditto

0

 

Disabled

●/●

5.14



0391

Preset-speed #11control mode

Ditto

0

 

Disabled

●/●

5.14



0392

Preset-speed #12 control mode

Ditto

0

 

Disabled

●/●

5.14



0393

Preset-speed #13 control mode

Ditto

0

 

Disabled

●/●

5.14



0394

Preset-speed #14 control mode

Ditto

0

 

Disabled

●/●

5.14



0395

Preset-speed #15 control mode

Ditto

0

 

Disabled

●/●

5.14



0396

Torque reference filter #2

10.0199.9, 200.0(No filters)

1/0.1

200.0

 

Enabled

●/●

/

6.21.2



0397

Speed loop proportional gain #2

3.21000

0.1/0.1

See J-28

 

Enabled

●/●

/●



0398

Speed loop integral gain #2

10.0200. 0 [rad/s]

0.1/0.1

See J-28

 

Enabled

●/●

/●