(Continued from the preceding page)

 

Item

Description

 

 

 

Warning

Stall prevention during operation, over-current suppression, overload, power

 

 

 

source-side undervoltage (optional), DC circuit undervoltage, setting error, retry in

 

 

 

message

 

 

 

process, upper/lower limits.

 

 

 

 

 

 

 

Fault

Overcurrent, over-voltage, heat sink overheat, load-side short-circuit, load-side ground

 

 

 

fault, inverter overload, armature over-current during start-up, load-side over-current

 

 

 

causes

during start-up, EEPROM error, RAM error, ROM error, transfer error (dynamic braking

 

 

 

trouble

resistor overload), (emergency stop), (undervoltage), (weak current), (over-torque),

 

 

 

 

(motor overload), (output open-phase). Items in parentheses are selectable.

 

 

 

 

Operation frequency, operation frequency command, operating direction

 

 

 

 

(forward/reverse), output current, DC voltage, output voltage, compensated frequency,

functions

LED

 

function

terminal board input /output information, CPU version, control EEPROM version, tripping

 

PBR overload rate, PBR load rate, power supply, output current, peak output current,

 

4-digit

 

Monitoring

history, cumulative operation time, speed feedback, torque, torque command, torque

 

7-segment

 

current, exciting current, PID feedback value, motor overload rate, inverter overload rate,

Display

 

 

 

peak DC voltage, motor counter pseudo PG, position pulse, RR input, VI/II input, RX

 

 

 

input, RX2 input, FM output, AM output, fixed output for meter adjustment, flash memory

 

 

 

version, main circuit EEPROM version, connection option types, previous default setting,

 

 

 

 

previous automatic control setting (AU2), sink/source switching status.

 

 

 

Selectable

Can select frequency display to match motor speed, line speed, etc. Selection of

 

 

 

unit display

display of current in amperes/%, voltage in voltage/%.

 

 

 

Edit

Parameters different from those set by default are retrieved automatically, so that

 

 

 

function

parameters changed can be detected easily.

 

 

 

User

Original parameters set by user can be stored. Parameters stored can be reset to

 

 

 

settings

original user-defined parameters.

 

 

 

initialization

 

 

LED

 

Charge

Indicates that main circuit capacitors are charged.

 

 

indicator

 

 

 

 

 

 

Input/output

terminal

A-contact/B-contact switchable by making a selection from the programmable I/O

logic switching

terminal function menu. (*1), (*2) (Default setting: A-contact)

Sink/source

 

Negative common (CC) and positive common (P24) of control terminal are switchable to

switching

 

each other. (On shipment, negative common [CC] is selected as default setting.)

 

Fault detection signal

1c contact output (250Vac-2A-cosΩ = 1,250Vac-1A-cosΩ = 0.4, 30Vdc-1A)

 

Low-speed/speed

 

 

reach signal

Open-collector output (24Vdc, Max. 50mA, output impedance: 33Ω)

signals

output (*2)

 

frequency output

Open-collector output (24Vdc, Max. 50mA, output impedance: 33Ω)

 

Upper/lower limit

 

Output

(*2)

 

 

 

Frequency meter

 

 

 

 

output/ammeter

Analog output, 1mAdc full-scale ammeter or 7.5Vdc-1mA voltmeter.

 

output (*3)

 

 

Pulse train

Open-collector output (24Vdc, Max. 50mA)

 

frequency output

 

Communication

RS485 equipped as standard (connector: modular 8P, optional device required for

communication with more than one unit)

functions

 

 

RS232C, TOSLINE-F10M and TOSLINE-S20 are optional.

 

 

 

 

conditions

Service

 

Indoor, altitude 1000m or less, not subject to direct sunlight or corrosive/explosive

temperature

is removed when the ambient temperature exceeds 40°C.)(*6)

 

environment

gas or steam.

 

Ambient

 

-10 to +50°C (For models 15 kW or less, Max. 50°C, provided that the upper cover

Service

 

 

Storage temperature

-25 to +65°C

 

Relative humidity

20 to 93% (no condensation allowed)

 

Vibration

 

5.9m/s2 {0.6G} or less (10 to 55Hz) (according to JIS C0911)

(*1): The 16 contact-input terminals (8 of which are optional) are programmable. For each of them, a signal can be selected from among 136 signals.

(*2): For each programmable ON/OFF output terminal, a signal can be selected from among 120 signals.

(*3): For each programmable analog output terminal, a signal can be selected from among 32 signals.

(*4): When the cover is removed, the unit must be placed in the panel to prevent the charger from being exposed. For the 30kW and larger models, the unit can be used in a temperature range of -10 to +50°C with the cover left attached.

(*5): The models with a capacity of 30kW or more have uncovered wide-opened wiring holes and the unit has no space in it which is large enough to bend external cables. So, use a optional wiring hole covers when installing the unit outside.

(*6): To use VFA7-2150P in 40 to 50°C, reduce the maximum output current to 80% of rated output current. Using VFA7-4150PL in 40 to 50°C, reduce the maximum output current to 85% of rated output current.

(*7): Protect the inverter from over-current caused by output-side ground fault.

K-4