6.12 PWM carrier frequency

 PWM carrier frequency

Function

1)The sound tone of acoustic noise can be changed by adjusting the PWM carrier frequency. This adjustment is effective in preventing the motor from resonating with its load(machine) or its fan cover.

2)Decreasing the carrier frequency is also effective in reducing electromagnetic.

Note) Decreasing the carrier frequency reduces electromagnetic noise but increases acoustic noise.

[Parameter setting]

Title

Function

Adjustment range

Default setting



PWM carrier frequency

(, ) [kHz](*1) [Upper limits differ by applicable motor capacity. Refer to the table below.]

Model

dependent

(*1)Setting the PWM carrier frequency larger than the default value, reduction of rated current is needed. For details, refer to figure and table below.

Rated current [%]

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Default setting

Upper limit

PWM carrier frequency [kHz]

Voltage

Applicable motor

PWM carrier freq. [kHz]

Rated current

 

Max value, no rated current

class [V]

capacity [kW]

Default setting

Upper limit

at upper limit [%]

 

reduction is needed [kHz]

 

0.42.2

12

 

15

No need of rated current reduction

 

5.51118.5

 

 

 

 

 

 

 

 

 

 

3.7

 

12

 

15

90

 

12

 

15

 

12

 

15

95

 

12

200

22

 

12

 

15

90

 

12

30

 

12

 

15

93

 

12

 

 

 

 

 

37

 

8

 

15

No need of

rated current reduction

 

45

 

8

 

15

80

 

8

 

55

 

2.2

 

8

85

 

3

 

7590

2.2

 

5

No need of

rated current reduction

 

0.752.2,

12

 

15

No need of rated current reduction

 

5.511, 18.5

 

 

 

 

 

 

 

 

 

 

3.71522

12

 

15

90

 

12

 

30

 

12

 

15

89

 

12

400

37

 

8

 

15

No need of

rated current reduction

45

 

8

 

15

80

 

11

 

 

 

 

 

55

 

8

 

15

65

 

8

 

75

 

2.2

 

8

70

 

4

 

90/110220

2.2

 

5

80

 

2.2

 

280

 

2.2

 

5

75

 

2.2

Note1) In vector control mode, set the carrier frequency to 2.2 [kHz] or over. Operation may become unstable if the carrier frequency is lower than 2.2 [kHz].

Note2) In the case that the operation frequency is more than 130Hz,carrier frequency is limited to less than 10kHz automatically.

Note3) Set the carrier frequency to 2.2kHz when sine wave filter (LFL,LFC)is used at output side of inverter. Filter can be damaged by fire in the case of other than 2.2kHz.

6.13 Trip-less enhancement

6.13.1 Auto-restart (restart during free-run (coast))

 Auto-restart

 Auto-restart adjustment #1

 Auto-restart adjustment #2

 Auto-restart mode

 Auto-restart adjustment #3

Warning

Mandatory

Do not get near the motor or the machine.

The motor and the machine unexpectedly restart after recovery from a momentary power failure, which might cause injury to persons.

Stick caution labels to the inverter, the motor and the machine, to prevent accidents due to an unexpected restart of them after recovery from a momentary power failure.

F-20

Page 111