[Message] The following are messages only. No trip is developed.

Indication

Contents

Expected causes

Countermeasures



ST-CC opened

ST terminal is in open-circuit.

Close ST-CC circuit.

 

Control circuit

Undervoltage between RO and

Measure supply voltage of control



SO of control power supply

power. If voltage is normal, it needs

 

undervoltage

(when option is used for 22 kW

repair service.

 

 

or lower type).

 

 

Main circuit

Undervoltage between R, S and

Measure supply voltage of main



T of main circuit power supply.

circuit power. If voltage is normal, it

 

undervoltage

Trouble of pre-charge circuit

needs repair service.

 

 

or DC circuit fuse.

Make a service call.

 

 

In retry operation.

If inverter automatically restarts

 

 

Momentary power failure is

dozens of seconds later, it is



Retry indication

occurred.

normal. Be careful of inverter in

 

 

 

retry status, because there is a fear

 

 

 

that it may suddenly restart.

 

Frequency point

Points 1 and 2 of frequency

Set points 1 and 2 of frequency



setting error

setting signal are set too close to

setting signal apart from each

 

alarm

each other.

other.



Clear enabling

If STOP key is pressed after trip

Press STOP key once more for

indication

indication, this indication

resetting.

 

appears.

 

 

 

 

 

Emergency stop

Stop operation is performed by

If STOP key is pressed, emergency



enabling

panel during automatic or

stop is executed. To cancel

remote operation.

emergency stop, press any other

 

indication

 

 

key.

 

 

 

 

Alarm for setup

Setup value error is detected in

Check setup value for input error.

 

value error

reading out or writing data.

 

 

(Error indication

 

 

/

and data are

 

 

 

alternately

 

 

 

displayed twice

 

 

 

each.)

 

 

 

 

Under DC braking

If message disappears dozens of



DC braking

 

seconds later, it is normal. (Note)

Under motor shaft fixing control

If message disappears by stop



indication

 

command (ST-CC open), it is

 

 

 

 

 

 

normal.

 

 

Number to be shown on panel

For indication of frequency, set



Panel indication

such as frequency and so on

multiplying rate () lower.

overflows figures of display.

(Parameter setting that results in



overflow

(Number of overflowing digits is

overflow is of course valid.)

 

 

 

 

indicated.)

 

 

 

Various transmission errors

For countermeasures against

 

 

occur when computer is linked

various transmission errors, refer to

 

Communication

up with inverter system.

the "Manual for communication".

Various transmission errors

Check the master inverter.

 

error

occur in inverter to inverter

 

 

 

 

 

 

communication (slave side).

 

 

 

Time-out or trip in master side.

 

 

Parameter is

Parameters are initialized to be

If message disappears dozens of



under

standard default values.

seconds later, it is normal.

 

initialization.

 

 

 In auto-tuning

Under auto-tuning.

If message disappears several seconds later, it is normal.

Note: In the case DC injection braking ON/OFF function is selected for an input terminal; if "" disappears as a result of open-circuit between the terminal and CC, it is normal.

[Pre-alarm display]

Indication

Contents

Expected causes and countermeasures

Overcurrent alarm

Same as  (over-current)

Overvoltage alarm

Same as  (over-voltage)

 

Achieving PBR operation level

P blink while PBR is operating is not an error.

Overload alarm

Same as  /  (overload)

Overheat alarm

Same as  (overheat)

When two or more alarms occur at the same time, such the message as shown in the following blinks. , , , ,・・・・・, 

Blinking indications appear in order of , , , from the leftmost place to right.

L-4